INSTALLATION
Translation of the original instructions
10
Installation operations, any conversion to other types of gas and start-up must only be
performed by qualified personnel, in accordance with current regulations.
Gas systems, electrical connections and premises where the appliances are installed must comply with
current regulations in the country of installation; in particular, the appliance must be installed in a room with
good ventilation, if possible under a suction hood to ensure complete evacuation of the exhaust gases
formed during combustion. The air required for combustion is 2 m3/h per kW of installed power. The
appliance can be installed alone or in series with other appliances in our production range. A minimum
distance of 10 cm between appliances must be respected to prevent contact with any walls made of
flammable material; furthermore, appropriate measures should also be adopted to ensure the thermal
insulation of flammable parts, such as the installation of heat shields; take special care to ensure that
appliances are installed in an appropriate and safe manner. The support feet can be adjustable in height and
any unevenness can therefore be eliminated.
GAS CONNECTION
The gas connection (see installation drawing) must be implemented using steel or copper pipes or steel
hoses, in compliance with applicable national standards. All appliances must be equipped with a gas shut-off
valve and fast-closing valve. Once installation is complete, make sure that there are no gas leaks from the
fittings; to do this, do not use a naked flame but substances that do not cause corrosion, such as solutions of
soapy water or leak detectors. All our appliances are subjected to detailed examination: the type of gas,
pressure in use and the pertinent category are indicated on the data plate (see attachment).
Note
The year of construction of the appliance is indicated under "N" on the data plate. The first 2 digits
indicate the year of construction.
·
THERMAL OUTPUT CONTROL
The appliances must be checked in order to verify that their thermal output is correct:
·
Thermal output is indicated on the appliance's data plate;
·
Firstly, make sure that appliance is set for the type of gas used and then make sure that the indication on
the data plate matches this gas. To adapt the appliance to another type of gas, make sure that the type of
gas in question complies with the information in this instruction manual.
Warning
Pressure is measured with a pressure gauge (minimum resolution of 0.1 mbar) mounted on
the appropriate socket. Remove the M6 locking screw and insert the pressure gauge tube.
The test must be performed with all the burners on the appliance switched on and all the
appliances in the same line switched on. After taking the measurement, replace the screw,
firmly tighten and check the seal.
Liquid gas connection G30 / G31
The liquid gas connection pressure is 30 mbar for butane and 37 mbar for propane. Check the data plate,
measure the pressure and verify that the description of the nozzle installed matches the information provided
by the manufacturer.
Methane gas connection H G20
The methane gas connection pressure is 20 mbar. Check the data plate, measure the pressure and verify
that the description of the nozzle installed matches the information provided by the manufacturer.
·
CHECKING THE PRIMARY AIR FOR MAIN BURNERS AND PILOT NOZZLE