Sometimes, it may be interesting to modify the measure by a simple terminal keyboard intervention. It can be used in 
many situations as sensor aging, an input refinement as a result of magnifying effect... 
 
To shift the measure, it is necessary: 
 

- To be in measure mode, 

 

- type on "

+

" or "

-

" to access the function, 

 

- on terminal display become: 

 
 

 

138.5 Ohms  

 

 

 

100.5 °C

 

 

Temperature value with offset, 

 

 

OFFSET 0.5 

 

offset function, temperature offset value. 

 
 

- Use keys 

"+"

 and 

"-"

 to adjust offset, the temperature is directly modified. 

 

- Type on 

"Enter"

 to save the new offset. 

 

 

 
OFFSET 

When the device is powered off and on, the offset stays active. To reset offset, it is necessary to enter in "OFFSET" 
mode, put the value to zero by "+" and "-" keys, then validate by <ENTER>.  
In offset mode, when there is no action on a key during 120 s, the device leaves automatically the mode and discard the  
new adjusted offset value and keeps the old offset value.

 

Summary of Contents for THL105

Page 1: ...S AND RIBBONS LOREME 12 rue des Potiers d Etain Actipole BORNY B P 35014 57071 METZ CEDEX 3 Phone 03 87 76 32 51 Contact Commercial Loreme fr Technique Loreme fr Download manual at www loreme fr CONFI...

Page 2: ...RATION p3 1 Hysteresis configuration p4 2 Delay configuration p4 3 End of configuration p4 RS232 LINK SETTING p5 TERMINAL MODE p6 Visualization p6 Configuration p6 1 Method p6 2 Configurable parameter...

Page 3: ...etpoint The button allows you to increment the setpoint and the button to decrement it The setpoint is incremented or decremented in steps of 1 C at the beginning Holding pressed the or button for mor...

Page 4: ...e Config button to validate the setting 0 to 50 C 2 Delay configuration RETARD Press the or button to increment or decrement the delay value 0 1 s steps 0s Press the Config button to validate the sett...

Page 5: ...ates another communication port number COMx and re quires the reconfiguration of the HyperTerminal The terminal emulation software for PC HyperTerminal is resident in windows up to XP version For late...

Page 6: ...modification by typing Enter The modification with simultaneous display followed by validation with Enter key 2 Configurable parameters The following parameters can be configured The threshold setpoin...

Page 7: ...s 100 5 C Temperature value with offset OFFSET 0 5 offset function temperature offset value Use keys and to adjust offset the temperature is directly modified Type on Enter to save the new offset OFFS...

Page 8: ...waiting mode This file is provide by LOREME This file contain the firmware code in intel HEX format Selected the Transfer Send a text file in the HyperTerminal menu Select the directory and open the...

Page 9: ...n fifty centimeters of a device with a transmitter walkie talkie of a power of 5 W be cause the latter can create a field with an intensity higher than 10 V M for a distance fewer than 50 cm 2 2 Power...

Page 10: ...Loreme fr Technique Loreme fr Wirings PC DEVICE LINK DIAGRAMS OF CONNECTIONS 3 terminals plug to THL105 LINK in FRONT FACE under the cover Female 9 terminals to PC 3 5 2 Cover lift here PT100 sensor P...

Reviews: