background image

 

SOMMAIRE

 

E 6  

LOREME

 12, rue des Potiers d'Etain - 57071 Metz  

 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: [email protected] - [email protected]

 

  RELAY 1?   

 

Push the 

 (yes) button to access to the relay 1 configuration. 

 
     THRESHOLD DETECTION? Push the 

 (yes) button to activate the detection, 

 (no) to deactivate it. 

 
     MEASURE: 

 

Choice of monitored measure type. 

     VOLTAGE? 

 

Push the 

 (yes) button to choose the displayed type.  

 

 

 

 

Push the 

 (no) button to display the next type. 

 
     HIGH THRESHOLD?   

Choose the type of detection (High or Low, see 

p11

). 

     LOW THRESHOLD? 
 
     THRESHOLD?   

 

Push the 

 (yes) button to access the threshold setting. 

 
      HYSTERESIS? 

 

Push the 

 (yes) button to access the hysteresis setting. 

 
     RELAY CLOSED IN ALARM? 

Choose the type of security. 

     RELAY CLOSED OUT OF ALARM? 
 
     ACTIVATION DELAY? 

Push the 

 (yes) button to access the activation delay setting. 

     DEACTIVATION DELAY? 

Push the 

 (yes) button to access the deactivation delay setting. 

 

or 

 
     ENERGY COUNT? 

Push the 

 (yes) button to activate the energy count, 

 (no) to deactivate it. 

 
     PULSE WEIGHT? 

Push the 

 (yes) button to access the counting pulse weight parameter (0.01 kWh minimum). 

 

  RELAY 2?   

 

Push the 

 (yes) button to access to the relay 2 configuration (only with option /R2). 

  

see relay 1.

 

 

4.5) Output configuration 

This rubric is only visible if the unit is equipped with an analogical output (/S option). 
 

OUTPUT CONFIG? 

Push the 

 (yes) button to access to the rubric. 

 
  CURRENT? 

 

Choose the output type, current or voltage. 

  VOLTAGE? 
 

  OUTPUT 0%? 

 

Push the 

 (yes) button to access the output low scale setting. 

 

  OUTPUT 100%?   

Push the 

 (yes) button to access the output high scale setting. 

 
  MEASURE: 

 

Choice of monitored measure. 

  VOLTAGE? 

 

Push the 

 (yes) button to choose the displayed type. Push the 

 (no) button to display the 

 

 

 

 

next type. 

 

  MEASURE 0%?   

Push the 

 (yes) button to access the measure low scale setting. 

 

  MEASURE 100%? 

Push the 

 (yes) button to access the measure high scale setting. 

 

  RESPONSE TIME? 

Push the 

 (yes) button to access the output response time (0 to 60 s). 

 

  LIMITATION? 

 

Push the 

 (yes) button to activate the output limitation, Push the 

 (no) button to  

 

 

 

 

deactivate the output limitation. 

 
See 

p12

 for more details about the output parameters. 

 
 

Summary of Contents for IPL36L

Page 1: ...meter LOREME 12 rue des Potiers d Etain Actipole BORNY B P 35014 57071 METZ CEDEX 3 Phone 03 87 76 32 51 Telefax 03 87 76 32 52 Contact Commercial Loreme fr Technique Loreme fr Download manual at www...

Page 2: ...nfiguration p8 5 Relays threshold setting visualization p8 RS232 LINK SETTING p9 TERMINAL MODE p10 1 Visualization p10 2 Configuration p10 2 1 Method p10 2 1 1 Menu selection p10 2 1 2 Parameter selec...

Page 3: ...Visualization At power on the device displays briefly its actual revision number It s a message of the form r x y where x is the hardware revision and y the software revision Then it displays the cur...

Page 4: ...current input 200 mV 200 A for the external shunt current input default shunt sensitivity is 1 A mV 4000 mV for the Hall sensor current input default configured caliber is 100 A The inputs configurati...

Page 5: ...ose the three phases mode or the no button to select the previous choice PT RATIO Push the yes button to access the PT ration setting 0 001 to 106 or the no button to go to the next rubric CT RATIO Pu...

Page 6: ...ergy count no to deactivate it PULSE WEIGHT Push the yes button to access the counting pulse weight parameter 0 01 kWh minimum RELAY 2 Push the yes button to access to the relay 2 configuration only w...

Page 7: ...es button to access to the rubric Use the buttons to increase decrease the value and the button to validate it The output factory address is 1 BAUD RATE Push the yes button to access to the rubric Use...

Page 8: ...measure mode without saving the new configuration 5 Setting or displaying the relays threshold If the threshold detection is activated pushing the button accesses to the threshold setting or displayi...

Page 9: ...another communication port number COMx and re quires the reconfiguration of the HyperTerminal The terminal emulation software for PC HyperTerminal is resident in windows up to XP version For later ve...

Page 10: ...ration mode just press C key The message ConF is displayed in front 2 1 Method during the configuration different types of questions are displayed For each one several answers are possible You will fi...

Page 11: ...eactivate the alarm on threshold overrun Threshold detection parameters are Monitored value voltage current frequency on IPL36 and IPL36L and active power reactive power apparent power power factor on...

Page 12: ...tion Response time The limitation allows to bound the output signal swing to the configured output scales for any input signal swing over flow The response time allows to smooth the TRMS measure rippl...

Page 13: ...play mode or N to choose the Y N YES fixed mode in kW kVAR kVA with 2 decimals 2 9 Special function This section allows you to lock the front face configuration access SPECIAL FUNCTION Press Y to acce...

Page 14: ...Byte first word 1 exponent mantissa MSB word 2 mantissa Data in 32 bits integer signed or not Data send MSB first 4 bytes or 2 words long Data in 16 bits integer format for status of alarm R1 bit0 and...

Page 15: ...ata The register address are the same as the table for MODBUS TCP This table lists the measures in 32 bits integer format and one 16 bits register for the alarms state address 18 The values given in t...

Page 16: ...rge A network higher load can cause communication error due to the traffic The average response time to a read request is around 50ms 3 Data explanation All measures are accessible in reading mode Dat...

Page 17: ...easures are at FFFFFFFF hexadecimal Register address in decimal Hexadecimal Designation Total words 4096 1000 Voltage V Word 1 1 Word 2 2 4098 1002 Current A Word 1 3 Word 2 4 4100 1004 Active Power W...

Page 18: ...Multiply the values of powers by the PT ratio and the CT ratio or external shunt sensibility and divide the result by 10 000 Register address in decimal Hexadecimal Designation Total words 0 000 Volt...

Page 19: ...ments of an IPL36 or IPL36L Click to refresh measures version number Tab for SNMP parameters Tab for password configuration IPL36 IPL36L There are no energy power power factor measurement 2 SNMP tab D...

Page 20: ...re details The MIB file can be downloaded directly on the Web page of the device 3 Security tab Limit the web server access with a password This length of this password is up to 8 characters This char...

Page 21: ...provide by LOREME and contain the firmware code in Intel HEX format Select the Transfer Send a text file in the HyperTerminal menu Select the directory and open the file The HyperTerminal program beg...

Page 22: ...elays thyristor power groups Do not get closer within fifty centimeters of a device with a transmitter walkie talkie of a power of 5 W be cause the latter can create a field with an intensity higher t...

Page 23: ...ption Analogical output mA terminals analog analog no jumper Analogical output V terminals analog analog need jumper between terminals analog 500 High voltage input terminals 600 V 0V Low voltage inpu...

Page 24: ...terminals L N Relay 1 terminals common C1 rest R1 work T1 Relay 2 terminals common C2 rest R2 work T2 High voltage input terminals 600 V 0V Low voltage input terminals 150 V 0V Current input terminal...

Reviews: