25
In-Band Alarm relay
Alarm tripped
Alarm reset
Alarm = In.Bnd
Hi = 69
Lo = 35
HI Set.Pt Value
The alarm relay will activate when the measured value is below the HI value and above the LO value
i n . b n d
h i
l o
Mode HI Setpoint value LO Setpoint value
LO Set.Pt Value
Out-Band Alarm relay
Alarm tripped
Alarm reset
Alarm = Out.Bnd
Hi = 69
Lo = 35
HI Set.Pt Value
The alarm relay will activate when the measured value is above the HI value or below the LO value
OUT.bnd
h i
l o
Mode HI Setpoint value LO Setpoint value
LO Set.Pt Value