ALARMS
ALARMS WITH IMMEDIATE COMPRESSOR SHUT-OFF
Code
Description
Cause
01
EMERGENCY STOP
Emergency stop button open (IN1)
02
MOTOR OVERLOAD
Thermal motor open (IN2)
03
THERMAL FAN
Thermal fan open (IN3)
04
NO PHASE
One or more phase missed for over 300 m.s.
05
WRONG PHASE
Phase inverted
07
DOOR OPEN
IN7 open (set as come door micro-switch)
09
DRIVE FAULT
Input relay fault drive open/closed (alarm managed with input enabled only
(C21=1/2))
11
HIGH PRESSURE
Working pressure over set WP2
12
T. PROBE FAILURE
Air end temperature probe failure
13
HIGH TEMP.
Air end temperature over set WT1
14
LOW TEMP.
Air end temperature lower than set WT5
15
SEPARATOR FILTER
Delta P (internal pressure – working pressure) over shut off set AP1 once the
timer C19.1 is over and air end temperature is over 45°C (alarm managed
when the aux pressure transducer is enabled into differential operation
(C19=2))
18
POWER OFF
In case of power off and compressor set as manual restart
20
TEMP. MOTORE
PTC input open
21
INPUT POWER FAULT
Safety pressure switch open (missing power to all digital inputs)
22
INPUT IN7
Parameter C12 = 3 (generic alarm)
25
SEPARATOR FILTER
Separator filter differential pressure switch open (IN6)
ALARMS WITH COMPRESSOR SHUT-OFF AFTER 30 SECONDS UNLOAD RUNNING
Code
Description
Cause
26
PRESS. TRANSD. FAILURE
Working pressure transducer failure
27
AUX. TRANSD. FAILURE
Aux. Pressure transducer failure
28
LOW VOLTAGE
Power supply to the controller lower than 9,5Vac and reset accepted when the
power goes over 10,6Vac.
It is not visualized in case it has been disabled in menu 4 Compressor SETUP
29
SAFETY
Timer CAF elapsed: this alarm is detected if the parameter Safety is set YES
30
HIGH TEMP. WARNING
Air end temperature over set WT2.
Reset once temperature is lower than WT2-5°C
32
CHECK COMPRESS.
Timer C—h elapsed: reset the related maintenance timer
33
RS 485 FAILURE
In case compressor start/stop is operated via RS232 and the watchdog
function is enabled (see MODBUS protocol communication)
60
INVERTER FAILURE
In case of inverter via RS485, shut off alarm detected (managed by inverter
connected via RS485 only (DR0>0))
62
COMMUNICATION INVERTER
No communication to inverter in case of connection via RS485 (managed by
inverter vua RS485 only (DR0>0))
NOTE
:
Every time a shut-off alarm is detected, both relay set as alarm led DL1 are activated; the alarm message is stored into the
alarm list; once the cause of the alarm has been erased, push the button
R
to reset the message and start the compressor.