M1-8 INVERTER RS485 (DANFOSS)
This menu allows to visualize/set the parameters related to the inverter in case of connection via RS485 (Danfoss available
only).
The parameters you can set, related setting range, default and password level necessary to the visualization and
modification are described in the table below:
Function
Description
Setting
Default
Password level
DR0
Drive Model
0/1
0
3
DR1
Min frequency
0Hz÷(DR2-5Hz)
30Hz
3
DR2
Max frequency
(DR1+5Hz)÷300Hz
85Hz
3
DR3
Accel. time
0.0s÷300.0s
40.0s
3
DR4
Decel. time
0.0s÷300.0s
4.0s
3
DR5
PID prop. gain
0.00÷99.99
4.40
3
DR6
PID int. time
0.00s÷99.99s
2.00s
3
DA0
Motor Power
0.00KW÷400.'KW
57.6KW
3
DA1
Motor Voltage
0V÷2000V
415V
3
DA2
Motor Frequency
8Hz÷200Hz
87Hz
3
DA3
Motor Current
0.1A÷999.9A
106.0A
3
DA4
Motor Speed
0RPM÷9999RPM
2575RPM
3
DA5
Current Limit
0.0%÷200.0%
100.0%
3
DA6
PID Diff.Time
0.00s÷99.99s
0.00s
3
DA7
Reset Energy Meter
0÷1
0
3
DA8
Jog Ramp Time
0.0s÷300.0s
20.0s
3
DA9
PID int. mult.
0.10÷4.00
1.00
3
Setup Drive
NOTE
:
If you set the parameter a value different from 0 on the parameter DR0, you enable the inverter operation via RS485 and
related alarms 60, 61,62.
After the last parameter DA9 comes “Setup Drive” that allows to start the setting of the inverter; it means to send the
parameters from DR1 to DA9 to the inverter. Moreover all the required settings to make the system LDrive
working, such as drive PID enable, drive PID setpoint and feedback source and so on, are programmed to the drive also.
Confirming “Setup Drive” the LCD visualizes the following screen:
In the middle of the LCD is visualized the drive status.
When the download is in progress, above the drive status comes the progress status (in percentage) of the setup.
Pressing
the setup start. Setup required approximately 5minutes.
Pressing R the setup abort and it is possible to go back to menu M1-8.
While setting up the inverter, the main contactor is activated.
Setup Drive
Drive ready