background image

390/390-2 DEL

MAGNETIC LOCKING SYSTEM

INSTALLATION AND PROGRAMMING 

1

Form 39990 Rev. E

09/23/2005

575 Birch Street, Forestville, CT 06010

Phone (866) 322-1237   Fax (866) 322-1233

WWW. LOCKNETICS .COM

390DEL

DELAYED EGRESS

MAGNETIC LOCKING SYSTEM

PLEASE READ ALL INSTRUCTIONS PRIOR TO INSTALLING THE ELECTROMAGNETIC LOCK.

HANDLE THE EQUIPMENT CAREFULLY

DAMAGING THE MATING SURFACES OF THE

ELECTROMAGNET OR THE ARMATURE MAY REDUCE LOCKING EFFICIENCY

.

General Description............................................. 2
Technical Specifications....................................... 2
Pre Installation Considerations............................ 3
Mechanical Installation.........................................4
Template Information............................................4
Wiring Information/Board Layout......................... 8
Terminal Layout/Dipswitch Settings..................... 9
100CAB/TR80/TR81 Hook-up..............................9
390-2 (Double Unit) Wiring Information.............. 10
Monitoring/Control Wiring and Examples.............11
Programming - General Information.................... 12
Code/iButton Functions........................................12
Keypad Initialization............................................. 13
“System 7” iButton Programming.........................13

Erasing Memory................................................... 13
Time Delay Settings............................................. 14
Automatic Relock Time Delay.............................. 14
Nuisance Alert Time Delay...................................14
Door Propped Open Alarm (SEC)....................... 14
Anti Tamper Switch Information........................... 15
Keypad Manual Programming............................. 16
iButton Manual Programming.............................. 18
TEP1 Initialization................................................ 18
Output Audible/Visual/Alarm Indication Table...... 18
Maintenance.........................................................21
Trouble Codes......................................................21
Error Codes..........................................................21
Overall Dimensions.............................................. 22

IMPORTANT! This manual is intended to be kept for programming, maintenance,
and trouble shooting purposes. 

Do not dispose of after installation.

Please present

this manual to facility manager upon completion of installation.

Summary of Contents for 390DEL

Page 1: ...tch Settings 9 100CAB TR80 TR81 Hook up 9 390 2 Double Unit Wiring Information 10 Monitoring Control Wiring and Examples 11 Programming General Information 12 Code iButton Functions 12 Keypad Initiali...

Page 2: ...wiring and manual programming aspects of the locks For computer programming see information provided with the software package you will be using THIS MANUAL COVERS THE 390 DEL AND 390 2 DEL DELAYED EG...

Page 3: ...may be necessary and the holes will have to be tapped Caution It is very important to make sure that magnet is secured to the structure of the opening Armature mounting hardware is for door thickness...

Page 4: ...late hole to allow the full range of adjustability C On the doors mark the locations of all holes Drill 2 1 4 dia holes per template for armature holder mount ing screws Armature mounting hole B is de...

Page 5: ...d with the pointed side facing away from the door and toward the armature It MUST be used for proper operation Use hex key to tighten the arma ture mounting bolt For solid core and hollow metal doors...

Page 6: ...e armature by applying pressure on each end of the magnet until fully mated together as shown below Mark the position of the mounting plate Remove mag net from the mounting plate without moving the mo...

Page 7: ...eads mounted on the access cover Pass these leads through the access hole on circuit board side of magnet Secure access cover Drive in anti tamper plugs using a rubber mallet NOTE Double units with SE...

Page 8: ...and DSM2 to board as shown Note that if the unit has only the DSM option connect the plug into the DSM1 jack If the unit has only the SEC and or BOCA option con nect the plug into the DSM2 jack If th...

Page 9: ...DELAYED EGRESS TIME 15 SECONDS 30 SECONDS ON DELAYED EGRESS TRIGGERED BY PLUNGER SWITCH ONLY DELAYED EGRESS TRIGGERED BY PLUNGER SWITCH OR AUX INPUT DELAYED EGRESS TRIGGERED BY PLUNGER SWITCH AND AUX...

Page 10: ...nch cables furnished standard with a double unit and one which comes with the SEC or BOCA options which are intended to connect the locks using plug in connectors to each other They may be extended if...

Page 11: ...ying power monitoring lock door and alarm status as well as fire alarm auxiliary release reset and timer inputs Note that most national codes require that magnetic locks become unlocked whenever a fir...

Page 12: ...ime delay functions can be entered using computer programming or by buttons located on the PC board The manual setting of time delays will still be possible even if manual programming of codes and or...

Page 13: ...ter entering up to seven iButtons wait 10 seconds for programming to end One quick beep will indicate that programming has ended E Return SW4 1 to its original position if required NOTE Whenever new S...

Page 14: ...xed at 1 second A Press and release SW3 the LED will begin flashing RED B Thereafter press SW2 once for each second of nuisance delay desired up to 3 seconds maximum Each SW2 activation will cause the...

Page 15: ...input or by entering a valid keypad code or iButton If power is applied while the cover is off the alarm will not sound Putting the cover on or depressing the ATS switch will arm it If the ATS switch...

Page 16: ...not unlock It will stay in alarm until a valid user code iButton or reset input will silence the alarm If the ATR option is pres ent and the unit was programmed by computer an access attempt will sho...

Page 17: ...r code Master Code 33 111 New Access Code 3 8 digits to end UP TO 150 NEW CODES CAN BE ADDED BY RETURNING HERE OR 191 New Toggle Code OR 115 New Lockout Code OR 113 New One Time Access Code OR 117 New...

Page 18: ...uch a iButton key up to the reader This iButton will be initialized as a MASTER iButton D Touch each iButton of the TEP1 to the reader in the following order two beeps of the audible will sound indica...

Page 19: ...Button 33 111 New PIN 3 8 digits New Access iButton to end UP TO 150 NEW iButtons CAN BE ADDED BY RETURNING HERE OR 191 New Toggle iButton OR 115 New Lockout iButton OR 113 New One Time Access iButton...

Page 20: ...Rev E 09 23 2005 The table below is intended to provide all possible indications and states which can be encoun tered under normal operation Note that some conditions or features are only available on...

Page 21: ...Armature magnet not installed properly p 5 6 DSM SEC option not working properly Armature holder not aligned with DSM SEC switch s Switch not plugged into correct jack p 8 MAINTENANCE It is not recom...

Page 22: ...390 390 2 DEL MAGNETIC LOCKING SYSTEM 22 Form 39990 Rev E 09 23 2005...