LockMaster SFG 18H User Manual Download Page 5

 

4

 

G. The Stop and/or Reset button must be located in the line-of-sight of the gate. Activation of the reset 
control shall not cause the opener to start. 
H. A minimum of two (2) WARNING SIGNS shall be installed, one on each side of the gate where easily 
visible. 

 

I. For a gate opener utilizing a non-contact sensor in accordance Usage Class: 
1) See instructions on the placement of non-contact sensors for each Type of application, 
2) Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor 
while the gate is still moving, and in the opening direction. 
3) One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, 
such as the perimeter reachable by a moving gate or barrier. 
J. For a gate opener utilizing a contact sensor in accordance with Usage Class: 
1) One or more contact sensors shall be located where the risk of entrapment or obstruction exists, such as 
at the leading edge, trailing edge, and post-mounted both inside and outside of a vehicular horizontal slide 
gate. 
2) One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate. 
3) One or more contact sensors shall be located at the pinch point of a vehicular vertical pivot gate. 
4) A hardwired contact sensor shall be located and its wiring arranged so that the communication between 
the sensor and the gate opener is not subjected to mechanical damage. 
5) A wireless contact sensor such as one that transmits radio frequency (RF) signals to the gate opener for 
entrapment protection functions shall be located where the transmission of the signals are not obstructed or 
impeded by building structures, natural landscaping or similar obstruction. A wireless contact sensor shall 
function under the intended end-use conditions. 
6) One or more contact sensors shall be located on the inside and outside leading edge of a sliding gate. 
Additionally, if the bottom edge of a sliding gate is greater than 6 inches (152 mm) above the ground at any 
point in its arc of travel, one or more contact sensors shall be located on the bottom edge. 
7) One or more contact sensors shall be located at the bottom edge of a vertical barrier (arm). 

Summary of Contents for SFG 18H

Page 1: ...www WholesaleGateOpener com Rev 11a...

Page 2: ...7 Installation Overview 8 Installation of the Opener 8 Manual Operation 9 Fit The Rack 9 Installation of the Limit Switch 11 Connecting of the Control Board 11 Setting of the Control Board 13 Test the...

Page 3: ...rrying out any work on the installation Also disconnect any buffer batteries if fitted Fit an omnipolar or magnetothermal switch on the mains power supply having a contact opening distance equal to or...

Page 4: ...lied for exposed rollers B The opener is intended for installation only on gates used for vehicles Pedestrians must be supplied with a separate access opening The pedestrian access opening shall be de...

Page 5: ...nside and outside of a vehicular horizontal slide gate 2 One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate 3 One or more contact sensors shall be locate...

Page 6: ...othly along its entire run and there is no excessive side slipping The opening and closing gate stops are positioned WARNING Remember that control devices are intended to facilitate gate operation but...

Page 7: ...6 It is suggestion that there is a 4 10cm distance at least between the gate edge and the gate wall when the gate is fully open Parts List...

Page 8: ...4 Dimensions 38 28 36 CM Class of gate opener I II Features Easy to install and low maintain Midway mode Quick selection for gate open close direction Reliable rolling code technology Emergency releas...

Page 9: ...pener You will need screwdrivers an electric drill wire cutters and a wire stripper a socket set and possibly access to a welder When install the opener you should build a concrete pad to support the...

Page 10: ...he lock cover Now the key slot appears 2 Insert the T handle Key provided to the key slot and turn it in counter clockwise 135 to disengage the clutch between the gear shaft and power output Now the o...

Page 11: ...from dealer if necessary 2 Put one end of rack section on the gear of opener as a temporary support Make rack level and mark the rack s mounting holes three holes on the gate 3 Weld the rack nut on t...

Page 12: ...nstall the magnet bracket so that the opener will stop at the desired open position when the open limit switch approaches it The higher magnet bracket must be installed at left side and lower magnet b...

Page 13: ...12 4 Alarm Lamp Optional One wire of the alarm lamp should be connected into the 4 terminal another should be connected into the 5 terminal...

Page 14: ...should be connected into the 12 terminal 9 Wired Keypad 12VDC Optional The RED wire of the wired keypad should be connected into the 12 terminal The BLACK wire of the wired keypad should be connected...

Page 15: ...to adjust the CLOSE stall force of the gate operator Turn the potentiometer clockwise to increase the stall force Turn the potentiometer counter clockwise to decrease the stall force Test the reversi...

Page 16: ...en erased How to use the remote to control the operator Key A is used to operate the operator to work alternately open stop close stop open When the Midway Mode function is enabled Key B is used to ac...

Page 17: ...ckets position b Please try to exchange the limit switch wires CL close and OP open There are two reed switches inside the magnetic limit switch one is upper and another is lower Maybe the magnet posi...

Page 18: ...www WholesaleGateOpener com 7106 S 220th St Kent WA 98032 USA sales WholesaleGateOpener com 2010 2012 LockMaster All Rights Reserved...

Reviews: