Sidewall direct venting
Sidewall termination – optional concentric vent
Multiventing sidewall terminations
When two (2) or more direct vent appliances are vented near
each other, each appliance must be individually vented (see FIG.
3-13). NEVER common vent or breach vent this appliance.
When two (2) or more direct vent appliances are vented near
each other, two (2) vent terminations may be installed as shown
in FIG. 3-13. It is important that vent terminations be made as
shown to avoid recirculation of flue gases.
Figure 3-13
Concentric Vent and Combustion Air Termination
Figure 3-12
Concentric Vent Sidewall Attachment
DO NOT use field-supplied couplings
to extend pipes. Airflow restriction
will occur and may cause intermittent
operation.
9. Cement appliance combustion air and vent pipes to the
concentric vent termination assembly. See FIG. 3-12
for proper pipe attachment.
10. Operate the appliance one (1) heat cycle to ensure
combustion air and vent pipes are properly connected
to the concentric vent termination connections.
CAUTION
Note:
100140480 shown for illustration purposes.
Installation & Service Manual
VENT
COMBUSTION
AIR
12"
MINIMUM
(TYPICAL)