8 OPERATING CODES/TROUBLESHOOTING
Installation, user and maintenance manual – LCGHP/LSGHP
61
CODES
DESCRIPTION
TRIP CONDITIONS
RESET METHOD
E 429
GAS SOLENOID VALVE WITHOUT
ELECTRICAL POWER
Code u_29 is active for more than 10 minutes
(with flame controller unit on).
Carry out appropriate checks. Reset may be performed from the
controller (or from the S61 board via menu 2, parameter 21). If the
code persists, contact authorised Technical Assistance.
u 430
GENERATOR FINS TEMPERATURE
HIGH
Temperature detected by Pt1000 probe high
Reset occurs automatically when the condition that generated the
code ceases
E 430
GENERATOR FINS TEMPERATURE
HIGH
Permanence of u_30 for 2 hours, or intervention
of u_30 for 12 times in 2 hours of operation.
Carry out appropriate checks. Reset may be performed from the
CCI/DDC (or from the S61 board via menu 2, parameter 1). If the
code persists, contact authorised TAC.
u 431
LIMIT THERMOSTAT FOR HEATING
MODULE ACTIVATED
Limit thermostat for heating module activated
Automatic as generating condition ceases. From DDC version 4.015
this error is not included in the Events’ log.
E 436
BLOWER FAULT
u_36 code generated three times in 1 hour of
operation.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 437
LOW COMBURENT AIR
TEMPERATURE
Air comburent temperature equal or smaller of
-10 °C
Reset occurs automatically when the condition that generated the
code ceases.
E 444
EVAPORATOR TEMPERATURE SEN-
SOR FAULT
Evaporator temperature probe fault
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
u 446
HOT INLET WATER TEMPERATURE
TOO HIGH
Hot inlet water temperature higher than upper
operating limit of the appliance (if the appliance
is in operation).
Resets automatically if, with the circulator on, the cause resolves or
(with circulator off) 20 minutes after generation of code.
u 447
LOW HOT WATER TEMPERATURE
Hot water temperature lower than lower operat-
ing limit of the appliance (if the appliance is in
operation).
Reset occurs automatically when cause resolves or 430 seconds
after the code is generated.
E 447
LOW HOT WATER TEMPERATURE
u_47 code generated 3 times in 1 hour of opera-
tion of the circulator.
Reset occurs automatically when the condition that generated
the code ceases. If the code persists, contact authorised Technical
Assistance.
u 448
HOT WATER DIFFERENTIAL TEM-
PERATURE TOO HIGH
High hot water differential temperature.
Reset occurs automatically 20 minutes after the operating code is
generated.
E 448
HOT WATER DIFFERENTIAL TEM-
PERATURE TOO HIGH
u_48 code generated twice in 2 hours of
operation.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21).
E 449
SATELLITE BOARD NOT PRESENT
Satellite board not present.
Reset occurs automatically when the condition that generated the
code ceases.
u 452
DEFROSTING FUNCTION ACTIVATED
Defrosting function activated. Defrosting is
activated if at least 90 minutes has passed since
the last defrosting (or 180 minutes if temperature
is inferior of -5°C), if the flame control unit has
been on for at least 15 minutes, and if room
temperature, temperature of hot inlet water and
of the evaporator require its execution.
The Code clears automatically when execution of defrosting ends.
u 453
WATER FLOW IN HOT PASSIVE
MODULE
Warning is generated if system operating in
conditioning mode and the flowmeter of the hot
module is closed.
Reset is automatic and occurs when the condition that generated
it ceases to apply.
u 478
OUTLET HOT WATER TEMPERATURE
TOO HIGH
Outlet hot water temperature too high
Reset is automatic and occurs when the condition that generated
it ceases to apply.
u 479
DEFROST FUNCTION ACTIVATED -
HOT SIDE
Activation takes place only if the
hot module is off and the antifreeze
function is enabled (see menu 1,
parameter 163).
Antifreeze function activated (with function
enabled: see menu 1, item163; and only with
machine off). In this case the antifreeze function
activates the plant water circulator. If this tem-
perature falls further to below 3 °C, the function
also activates the flame controller.
Resets automatically (defrost function disabled) if, with only the
circulator operating, the hot water inlet/outlet temperature rises
above 5°C (at which point the circulator switches off); or, if also the
flame controller is on, when the temperature reaches 18 °C (in this
case the flame controller and then the circulator switch off).
u 480
INCOMPLETE PARAMETERS
Incomplete parameters.
The code remains until operating parameters are entered and
completed. Contact authorised Technical Assistance. If the board is
replaced, Code E 80 may appear; this means that the unit’s charac-
terisation parameters have not been set.
E 80/480
INVALID PARAMETERS
Invalid parameters or damage to parameter
memory.
Reset occurs automatically when correct parameters are entered.
If the code persists, contact authorised Technical Assistance: if the
parameters are incorrect, it is necessary to enter and complete the
unit operating and characterisation parameters; if the memory is
damaged, the controller must be replaced.
u 481
INVALID BANK 1 PARAMETERS
Invalid Bank 1 data - Bank 2 data OK.
Reset occurs automatically 5 seconds after the code is generated.
E 481
INVALID BANK 1 PARAMETERS
The program attempts to resolve the problem by
writing the second page over the first; if after 5
attempts this fails, the error is generated.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
u 482
INVALID BANK 2 PARAMETERS
Invalid Bank 2 data - Bank 1 data OK.
Reset occurs automatically 5 seconds after the code is generated.
E 482
INVALID BANK 2 PARAMETERS
The program attempts to resolve the problem by
writing the first page over the second; if after 5
attempts this fails, the error is generated.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 484
FAULTY TRANSFORMER CONNEC-
TION OR 24 V AC FUSES
Damage to one of the 2 24-0-24 V AC transformer
fuses, or one of 24-0-24 V AC wires to the board
not supplying current.
Check fuses and 24-0-24 V AC electrical power connections on the
controller. Reset may be performed from the controller (or from the
S61 board via menu 2, parameter 21). If the code persists or occurs
again, contact authorised Technical Assistance.
E 485
INCORRECT MODULE TYPES (from
menu 6)
The set module type (from menu 6) does not cor-
respond to the one managed by the controller.
Reset occurs automatically when correct parameters are entered. If
the code persists, contact authorised Technical Assistance.
E 486
MEMORY TEST UNSUCCESSFUL
Processor error.
Contact authorised Technical Assistance.
E 487
MEMORY TEST UNSUCCESSFUL
Processor error.
Contact authorised Technical Assistance.
E 488
MEMORY TEST UNSUCCESSFUL
Processor error.
Contact authorised Technical Assistance.
E 489
MEMORY TEST UNSUCCESSFUL
Processor error.
Contact authorised Technical Assistance.