background image

10

3  

Operation

Hot Water Generator Installation and Operation Manual

After all installation procedures have been completed, and all
water, energy source joints, and power connections have been
double checked, the unit is ready for operation.

As a

precaution, it is strongly suggested that the following Startup
and Shutdown procedures be followed.

Startup procedure

1.

Assure that all manual shutoff valves on the water and 
energy source lines are closed.

2.

Slowly open the manual shutoff valve on the cold water 
inlet line, checking to assure that there are no leaks at the 
valve or any joints. Allow the tank to fill with water. As 
the tank is filling, hold the pressure relief valve open to 
allow air to bleed out of the tank. This will speed the 
filling process.

3.

Adjust the operating temperature control to the desired 
operating temperature.

4.

Set the high temperature limit thermostat at 10 to 15 
degrees Fahrenheit (10°F to 15°F) above the desired 
operating temperature.

5.

If the unit is so equipped, turn on the internal circulating 
pump. The circulating pump will operate constantly as 
long as power is supplied to the pump.
Shutoff valves are located on the inlet and/or outlet side 
of the circulating pump line. These valves should be 
opened before the pump is turned on. After the power to 
the pump is turned on verify that the pump is working.
If the pump is an oil lubricated unit, verify proper oiling.

6.

Open the valve on the condensate drain line, or boiler 
water return line.

7.

For steam to water controls, slowly open the manual 
shutoff valve on the steam inlet. Create a load/demand 
situation of approximately 10 to 25% of the system 
design conditions.

As the valves are being opened,

check for leaks at the valves and all pipe joints.

8.

For water to water controls, slowly open the manual 
shutoff valves on the boiler water inlet and outlet lines.
Create a load/demand situation of approximately 10 to 
25% of the system design conditions. As the valves are 
being opened, check for leaks at the valves and all pipe 
joints. Open the bypass loop ball valve approximately 
half way. Allow the system to push air out of the tube 
bundle and the piping slowly.

Note:

It should be noted that when the control valve is closed

the boiler water will flow through the bypass loop. When the
valve is open, less water will “bypass”. Adjustment of the
bypass loop ball valve will be necessary to balance your
system. For initial installation the bypass valve should be
closed.

WARNING

Steam or boiler water present situations
that can be very dangerous because of the
high temperatures and pressures.

Use

common sense and follow all accepted and
recommended procedures when
performing installation, operation, and
maintenance procedures to avoid possible
injury or death.

9.

Turn on power to the rest of the electrically controlled 
components of the unit (if equipped).

10. As the unit is initially heating the water, carefully 

re-inspect cold water inlet, hot water outlet, steam inlet 
(or boiler water inlet), and condensate return (or boiler 
water return line) joints for signs of leakage.

11. As the unit approaches the desired operating 

temperature, adjust the temperature control valve.

12. After the unit has reached operating temperature, re-

inspect all joints for signs of leakage. In addition, check 
all gauges and controls to verify that the water 
temperature and pressure, as well as energy source 
pressure, are within design specifications.

13. The unit is now ready for normal operation.

Shutdown procedure

1.

Turn off all power to the circulating pump and/or electric 
controls, if equipped.

2.

Close all valves in the steam inlet line (or boiler water  
line).

3.

Relieve the pressure from the energy source line (steam or 
boiler water), where possible.

4.

Close all remaining valves in the system in this order:
• the hot water outlet line;
• the cold water inlet line; and
• the condensate return line (or boiler water return line) 

5.

After  the system has cooled, drain the unit by opening 
the tank drain valve and holding the pressure relief valve 
in the open position. This will prevent the formation of
a vacuum and increase the drainage flow.

6.

Proceed with the required maintenance or repairs.

7.

After performing the required maintenance or repairs,
return the unit to operation by following the Startup 
Procedure.

Summary of Contents for Hot Water Generator

Page 1: ...ion contained in this manual is intended for use by qualified professional installers or service technicians Consult your local expert for proper installation or service procedures WARNING Save this manual for future reference Unit shown with optional control package ...

Page 2: ...mportant information concerning the life of the product DANGER WARNING CAUTION CAUTION NOTICE DANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION indicates a potentially hazardous situation which if not avoided may resul...

Page 3: ...ey are installed Hot Water Generator Systems are available in horizontal or vertical configurations see FIG s 1 and 2 in a wide array of gallon capacities Standard packages are available in tank sizes from 200 1000 gallons with single wall copper tube bundle heating units Custom configurations smaller and larger tank and tube bundles and optional control packages are also available Consult the fac...

Page 4: ...and outlet wye strainers a float and thermostatic steam trap and all necessary piping Water to Water Control packages include isolation valves 2 way self operated temperature regulator inlet wye strainer and all necessary piping Options Manual Reset High Limit Solenoid Valve Manway see notes on manway 150 psi Tank Working Pressure Temperature Pressure Gauge Vacuum Breaker Figure 1_Vertical Tanks F...

Page 5: ...ves and pressure regulators 3 All power connections and cables Before attempting any installation operation or maintenance procedures pertaining to this unit 1 Assure that the incoming steam or boiler water has been turned off at the manual shutoff valve 2 If the unit has been in operation allow the water in the heater and all components and surfaces incoming steam line hot water outlet line etc t...

Page 6: ...ory after leak testing Reassembly will require re attaching the unions or bolting flange to the appropriate locations and insertion of the control valve bulb into the provided bulbwell and the system is ready for operation see FIG s 5 and 6 below All hardware for the reassembly is included with the system Drawings of the specific controls package are included with each product illustrating the fin...

Page 7: ...drawings that indicate the location and specifications for each connection that must be made In addition the drawing will enable the installer s to determine the flow direction of both the water and energy source Connecting the cold water source and the hot water outlet Before making any connections of water inlet or outlet to the unit assure that all piping is clean and free of foreign material o...

Page 8: ...f valve should be installed downstream in the condensate return line to allow the unit to be isolated from the system The condensate shutoff valve will prevent backflow of steam if the line is disconnected WARNING Do not attempt to lift condensate with a float and thermostatic trap Pipe the condensate outlet from the main steam trap to a gravity drain or to a condensate pump Lifting condensate wit...

Page 9: ...must be connected The circulation pump must run all the time Wire this pump to a correctly sized disconnect switch per local codes The combination of electricity and water can pose a very dangerous situation Assure that all electric power has been turned off before attempting any installation or maintenance procedures WARNING Reference the wiring CAD drawing included with the unit or the installat...

Page 10: ...ypass loop ball valve approximately half way Allow the system to push air out of the tube bundle and the piping slowly Note It should be noted that when the control valve is closed the boiler water will flow through the bypass loop When the valve is open less water will bypass Adjustment of the bypass loop ball valve will be necessary to balance your system For initial installation the bypass valv...

Page 11: ...ns R RE EC CO OM MM ME EN ND DE ED D I IN NS SP PE EC CT TI IO ON NS S To Be Inspected Time Interval Per Manufacturer Specs Weekly Monthly Quarterly Semi Quarterly Annually Circulating Pump Control Valves Temperature Pressure Gauges Pressure Temperature Lines Inlet Outlet Return Power Connections Pressure Relief Valve Shutoff Valves Manual Single Solenoid Safety System Strainers Temperatures Water...

Page 12: ...gn pressure for energy source in the tube bundle as the temperature of the water in the tank heater approaches shutoff Reconfigure the condensate water return piping and check valve to allow for proper drainage Check to assure that there is no restriction in the condensate water drain line Replace the check valve if it is leaking or has failed Also check to assure that there is no restriction in t...

Page 13: ...he tank heater approaches shutoff Reconfigure the condensate water return piping and check valve to allow for proper drainage Check to assure that there is no restriction in the condensate water drain line Replace the check valve if it is leaking or has failed Also check to assure that there is no restriction in the condensate water drain line Verify control valve bulb was installed in the bulbwel...

Page 14: ...stem has failed Check the individual components of the system and repair or replace the failed component s as necessary A loud banging in the water heater primary piping or condensate water return piping not to be confused with a normal clicking noise made during operation The condensate water return piping has not been installed properly allowing the condensate water to drain freely by gravity th...

Page 15: ... may have entered the storage tank during the draining process Close the hot water tap if no air discharge is observed 9 Turn on electric power to the circulating pump and other electrical components if necessary 10 Observe tank and piping to ensure all components are functioning properly Cleaning the storage tank The mineral accumulation in an un fired tank will be in a soft sediment form that ca...

Page 16: ...m anode rod inspection Glass lined storage tanks have a magnesium anode s to provide cathodical protection of the lining and minimize corrosion Aggressive water conditions in some areas of the country may accelerate the deterioration of the anode s The anode s should be periodically removed and inspected to determine if replacement is necessary The tank must be valved off from the system and fully...

Page 17: ...nce FIG 9 to assure proper wiring 9 Follow the startup procedures page 10 to put the unit back on line Carefully check all connections for any sign of leakage Circulating pump shutoff valves replacement If the Lochinvar Hot Water Generator is equipped with a circulating pump to assist in the even heating of the water manual shutoff valves will be located on both the inlet and outlet side piping To...

Page 18: ...y drained that the pressure has been bled from both the water and energy source systems and that the water all components and surfaces have cooled 3 Carefully break the connections between the tube bundle head and the energy source inlet and outlet lines WARNING It may be necessary to break the lines at a second location and for the lines to be rotated to allow clearance for the tube bundle to be ...

Page 19: ...e damaged section of line or valve 6 Reconnect the line or valve to the unit Follow recommendations contained in the manufacturer s documentation local codes or accepted contractor practices as to the use and or type of joint compound or sealer at the connections 7 Follow the startup procedures page 10 to put the unit back on line Carefully check all connections for any sign of leakage Single sole...

Page 20: ... it is necessary care should be taken to ensure that in line components are not damaged 7 Remove the temperature control valve from the system 8 Follow the supplied manufacturer instructions for inspecting the valve If found to be malfunctioning replace the valve 9 Carefully replace the temperature control valve into the system by reattaching it to the energy source inlet line and the tube bundle ...

Page 21: ...ning properly and must be replaced follow the procedure outlined below WARNING The combination of electricity and water can pose a very dangerous situation Turn off disconnect all electric power before attempting any maintenance procedure 1 Follow Steps 1 through 5 of the shutdown procedure page 10 to take the unit off line before attempting to replace the main or auxiliary traps 2 The exact locat...

Page 22: ...22 Hot Water Generator Installation and Operation Manual 7 Notes ...

Page 23: ...23 7 Notes Hot Water Generator Installation and Operation Manual ...

Page 24: ...HWG i o 01 CP 2M 12 05 ...

Reviews: