AIR SUPPLY
The following information is based on single water heater installations only. If more than one water heater is being used, BS6644 should be
consulted to calculate the necessary requirements.
11.1
COMBUSTION VENTILATION
When used as a Type C appliance, provided sufficient clearance is provided, ventilation for combustion is not necessary as the combustion air
is ducted directly from outside.
When used as a Type B appliance, the combustion air requirements are as follows:
Model
Gross
Input
(kW)
Net
Input
(kW)
Ventilation
(Room)
(cm
2
)
Compartment
Compartment
(Direct to Outside)
(To Internal Space)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
SHW35-245CE
36.6
33.3
132
166
332
332
664
SHW46-325CE
43.9
39.6
165
200
400
400
800
SHW61-325CE
58.6
52.8
230
265
530
530
1060
COMBUSTION
VENTILATION
REQUIREMENTS
SHW35-245CE
–
SHW61-325CE
Model
Gross
Input
(kW)
Net
Input
(kW)
Plant Room
Enclosure
Low
Summer Use
Medium
Summer Use
High
Summer Use
Low
Summer Use
Medium
Summer Use
High
Summer Use
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
SHW86-410CE
83.5
75.3
152
304
228
380
304
456
380
760
456
836
532
912
SHW116-410CE
117.2
105.6
212
424
318
530
424
636
530
1060
636
1166
742
1272
SHW146-410CE
146.5
132.0
264
528
396
660
528
792
660
1320
792
1452
924
1584
COMBUSTION
VENTILATION
REQUIREMENTS
SHW86-410CE
–
SHW146-410CE
11.2
COOLING VENTILATION
When used as a type C appliance, cooling ventilation should be provided as follows:
Model
Input
(Gross)
kW
Input
(Net)
kW
Enclosure/Compartment
Enclosure/Compartment
Internal Space/Boiler Room
(Direct to Outside)
(To Internal Space)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
SHW35-245CE
36.6
33.2
166
166
332
332
N/A
N/A
SHW46-325CE
43.9
39.6
200
200
400
400
N/A
N/A
SHW61-325CE
58.6
52.8
265
265
530
530
N/A
N/A
SHW86-410CE
83.5
75.3
380
380
760
760
152
152
SHW116-410CE
117.2
105.6
530
530
1060
1060
212
212
SHW146-410CE
146.5
132.0
660
660
1320
1320
264
264
COOLING
VENTILATION
REQUIREMENTS
When used as a type B appliance, provision for cooling ventilation is included in the combustion ventilation allowance.