22
3
General
venting
Installation & Operation Manual
Figure 3-8 Near Water Heater Stainless Steel Venting
The installer must use a specific vent starter
adapter at the flue collar connection,
supplied by the vent manufacturer to
adapt to its vent system. See Table 3F for
approved vent adapters. Discard CPVC
starter piece.
NOTICE
Stainless steel vent
This product has been approved for use with stainless steel
using FasNSeal vent systems.
Use only the materials, vent systems, and
terminations listed in Table 3F. DO NOT
mix vent systems of different types or
manufacturers. Failure to comply could
result in severe personal injury, death, or
substantial property damage.
WARNING
Installations must comply with applicable
national, state, and local codes. Stainless
steel vent systems must be listed as a
UL-1738 approved system for the United
States and a ULC-S636 approved system
for Canada.
NOTICE
Installation of a stainless steel vent system
should adhere to the stainless steel vent
manufacturer’s installation instructions
supplied with the vent system.
NOTICE
STAINLESS STEEL VENT TERMINATION KITS
Model
Kit Part Number
Component Description
SB 1000 - 1500
KIT30028
6" PVC x 6" Stainless Steel Adapter
6" Stainless Steel Vent Termination
6" Stainless Steel Air Inlet
SB 1300 - 1500
KIT30029
6" PVC x 6" Stainless Steel Adapter
6" Stainless Steel x 7" Stainless Steel Adapters (2)
7" Stainless Steel Vent Termination
7" Stainless Steel Air Inlet
METAL FAB
Model
S.S. Adapter
Flue Termination
Intake Air
Termination
SB 1000 - 1500
6FCGLXL
6FCGSWMC
6FCGSWC
6FCGSW90L
Table 3F Approved Stainless Steel Terminations and Adapters
The Armor X2 uses model specific combustion air intake and
vent piping sizes as detailed in Tables 3A and 3B.
Increasing or decreasing combustion air
or vent piping to sizes not specified in this
manual is not authorized.
NOTICE
PVC/CPVC or ABS is acceptable air inlet pipe material.
NOTICE