Page | 17
9
16
1
C
OMPRESSOR CAPACITY STEPS
Model
No Of Compressors
1
2
3
4
302
50%
50%
--
--
402
50%
50%
--
--
602
50%
50%
--
--
702
50%
50%
--
--
902
50%
50%
--
--
1202
50%
50%
--
--
1402
50%
50%
--
--
1804
25%
25%
25%
25%
2304
25%
25%
25%
25%
2604
25%
25%
25%
25%
C
ORRECTION TABLES
Operation with glycol
Glycol percentage
Freezing point (°C)
CCF
IPCF
WFCF
PDCF
10
-3.2
0.985
1
1.02
1.08
20
-7.8
0.98
0.99
1.05
1.12
30
-14.1
0.97
0.98
1.09
1.22
40
-22.3
0.965
0.97
1.14
1.25
50
-33.8
0.955
0.965
1.2
1.33
CCF: Capacity correction factor
IPCF: Input power correction factor
WFCF: Water flow correction factor
PDCF: Pressure drops correction factor
The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation
without glycol. The water flow rate correction factor is calculated in order to maintain the same temperature
difference as that which would be obtained without glycol. The pressure drop correction factor takes into account
the different flow rate obtained from the application of the flow rate correction factor.
Correction
data tables at different Δt
Water temperature diff.(°C)
3
5
8
CCCP
0.99
1
1.01
IPCF
0.99
1
1.02
CCCP = Cooling capacity correction factor IPCF = Input power correction factor
Correction tables different Fouling factors
Fouling factor
0.00005
0.00001
0.00002
CCCP
1
0.98
0.94
IPCF
1
0.98
0.95
CCCP = Cooling capacity correction factor IPCF = Input power correction factor
Summary of Contents for Amicus LAHP1202WW
Page 27: ...Page 27 HYDRAULIC COMPONENTS O Flow Switch N User heat exchanger Q Source heat exchanger O Q N...
Page 33: ...33 P a g e Remote wiring connections optional...
Page 34: ...34 P a g e Factory fitted wiring connections...
Page 55: ...Dimensional Drawing Amicus LAHP WW Units 1804 2304 2604...
Page 56: ...NOTES...
Page 57: ...NOTES...
Page 58: ......