Ratings
Notes:
1. Outdoor Armor water heaters are supplied with
special gas venting materials. Use only the method of
installation specified in the Outdoor Armor Installation
and Operation Manual.
2. Standard outdoor Armor water heaters are equipped
to operate from sea level to 4,500 feet
only
with no
adjustments. The water heater will de-rate by 4% for
each 1,000 feet above sea level up to 4,500 feet.
3. The manual reset high limit provided with the outdoor
water heater is listed to UL353. The auto reset high
limit is listed to ANSI Z21.87.
7
Maximum allowed working pressure is located on the rating plate.
NOTICE
Model Number
Note: Change “N”
to “L” for L.P. gas
models.
CSA
Input Modulation Btu/hr
Water Content
Gallons
Water
Connections
Gas
Connections
(Note 2)
OAN151PM
30,000 - 150,000
1.3
1-1/4"
1/2"
OAN200PM
40,000 - 199,999
1.7
1-1/4"
1/2"
OAN286PM
57,000 - 285,000
2.4
2"
3/4"
OAN400PM
80,000 - 399,999
3.4
2"
1"
OAN501PM
100,000 - 500,000
4.2
2"
1"
OAN601PM
120,000 - 600,000
4.2
2"
1"
OAN701PM
140,000 - 700,000
5.0
2"
1"
OAN801PM
160,000 - 800,000
5.7
2"
1"
HLW
Outdoor Armor Water Heater
Installation & Operation Manual