background image

I509 GB I 09 17

31100345

G

B

2

CONTENTS

PAGE

Introduction ........................................................................................................................................................................................................................................................................................................................

2

Description .........................................................................................................................................................................................................................................................................................................................

2

Front button functions  ........................................................................................................................................................................................................................................................................................................

2

Display indications ..............................................................................................................................................................................................................................................................................................................

2

Displaying measurements   .................................................................................................................................................................................................................................................................................................

3

Main page  ...........................................................................................................................................................................................................................................................................................................................

3

Front metrology LED  ..........................................................................................................................................................................................................................................................................................................

3

Table of display pages  ........................................................................................................................................................................................................................................................................................................

4

Navigating between the display pages ................................................................................................................................................................................................................................................................................

6

Energy meter indication ......................................................................................................................................................................................................................................................................................................

7

Tariffs ..................................................................................................................................................................................................................................................................................................................................

7

Hour counter indication  ......................................................................................................................................................................................................................................................................................................

7

Limit threshold status indication (LIMx) .............................................................................................................................................................................................................................................................................

8

Alarm indication ..................................................................................................................................................................................................................................................................................................................

8

Main menu ..........................................................................................................................................................................................................................................................................................................................

8

Parameters setting (setup)  .................................................................................................................................................................................................................................................................................................

8

Parameter table  ..................................................................................................................................................................................................................................................................................................................

9

Commands menu  ...............................................................................................................................................................................................................................................................................................................

12

Wiring test  ..........................................................................................................................................................................................................................................................................................................................

12

Wiring diagram  ...................................................................................................................................................................................................................................................................................................................

12

Terminals arrangement and mechanical dimensions (mm)  ................................................................................................................................................................................................................................................

13

Technical specifications  ......................................................................................................................................................................................................................................................................................................

14

INTRODUCTION
The three-phase energy meter with CT insertion, model DME D305T2MID, has been designed to combine the utmost ease of use with a wide range of advanced functions. Despite the extremely limited dimensions of
the modular housing (just 4 modules), the energy meter features the same performance as a high-level device. The backlit LCD display permits a clear and intuitive user interface. The DME D305T2MID also features 
2 static outputs for pulse generation and a tariff input.

DESCRIPTION 
–   Three-phase energy meter
–   CT insertion
–   4U (72 mm) modular construction for DIN rail
–   Backlit LCD display
–   2 static outputs
–   AC tariff input
–   3 navigation buttons for functions and settings
–   Metrology LED for energy flow indication
–   High-accuracy true root mean square (TRMS) measurement
–   Active energy measurement according to EN50470-3 class B
–   Active and reactive energy meters, total and by individual phase
–   Total and partial energy meters (only partial meter can be reset)
–   1 total hour counter and 4 partial hour counters
–   Programmable input (e.g. for tariff selection)
–   2-level password protection for settings
–   Backup copy of original settings
–   Fitting does not require tools
–   Terminal covers that can be lead sealed
–   Texts in 6 languages (English, Italian, French, Spanish, Portuguese, German).

KEYBOARD FUNCTIONS

and 

buttons 

– Used to scroll between screens, select from available options on the display and change (increase/decrease) settings.

When pressed simultaneously (

+

), they are used to enter or exit the various display and setup menus.

button 

– Used to scroll sub-pages, confirm selected options and switch between display modes.

DISPLAY INDICATIONS

 
 
 

 

Main measurements 

display 

Alarm icon 

Sub-page 

(measurement 

type) indication 

Main 

measurements 

display 

Measurement page 

indication 

Bar graph 

Communication 

active

 

Selected 
phase(s) 
indication

 

Bar graph full 
scale 
indication 

Summary of Contents for DME D305T2MID

Page 1: ...nd vom Bediener leicht zugänglich sein Er muss als Trennvorrichtung für das Gerät gekennzeichnet sein IEC EN 61010 1 6 11 2 Das Gerät mit einem weichen Tuch reinigen keine Scheuermittel Flüssigreiniger oder Lösungsmittel verwenden ADVERTENCIA Leer atentamente el manual antes de instalar y utilizar el regulador Este dispositivo debe ser instalado por personal cualificado conforme a la normativa de ...

Page 2: ...mm modular construction for DIN rail Backlit LCD display 2 static outputs AC tariff input 3 navigation buttons for functions and settings Metrology LED for energy flow indication High accuracy true root mean square TRMS measurement Active energy measurement according to EN50470 3 class B Active and reactive energy meters total and by individual phase Total and partial energy meters only partial me...

Page 3: ...s allow the measurement display pages to be scrolled one at a time The current page can be recognized through the unit of measurement shown in the top part of the display Some measurements may not be displayed depending on the programming and the connection for the device for example if programmed for a system without neutral the measurements relating to neutral are not displayed For every page th...

Page 4: ...TOT 12 ENERGY METERS L3 kWh L3 PAR SYS TAR 1 TAR 2 kWh L3 TOT 13 ENERGY METERS L1 kvarh L1 PAR SYS TAR 1 TAR 2 kvarh L1 TOT 14 ENERGY METERS L2 kvarh L2 PAR SYS TAR 1 TAR 2 kvarh L2 TOT 15 ENERGY METERS L3 kvarh L3 PAR SYS TAR 1 TAR 2 kvarh L3 TOT 16 ENERGY METERS L1 kvarh L1 PAR SYS TAR 1 TAR 2 kvarh L1 TOT 17 ENERGY METERS L2 kvarh L2 PAR SYS TAR 1 TAR 2 kvarh L2 TOT 18 ENERGY METERS L3 kvarh L3...

Page 5: ...N VOLTAGE HARMONIC DISTORTION THD V L1 THD V L2 THD V L3 HI LO AV 36 CURRENT HARMONIC DISTORTIONE THD I L1 THD I L2 THD I L3 HI LO AV 37 HOUR COUNTER hhhhhh mm ss TOT PAR 1 PAR 2 PAR 3 PAR 4 38 LIMIT THRESHOLD LIM1 LIM2 LIM3 LIM4 39 ALARMS ALA1 ALA2 ALA3 ALA4 40 SELECTED TARIFF tAr 1 and tAr 2 41 INFO REVISION SERIAL NO MODEL REV SW SER No NOTE The pages highlighted in grey in the above table may ...

Page 6: ...m value Minimum value Average value Instantaneous value Maximum value Minimum value Average value Instantaneous value Maximum value Minimum value Average value Instantaneous value Max Demand value Maximum value Minimum value Average value Phase to neutral voltages Phase and neutral currents Active power phase and total ...

Page 7: ...e 2 independent tariffs in addition to total and partial The tariff is normally selected through the digital input or optionally through messages sent through the communication protocol To select the 2 tariffs the TAR A input function is available Activating this makes the selection illustrated in the table The device features a VAC programmable input The default function setting is TAR A which th...

Page 8: ... alarm reset method depends on parameter P09 n 03 This determines whether it can be automatic on the disappearance of the alarm conditions or requires manual intervention through the commands menu C 07 MAIN MENU To access the main menu Press and simultaneously The main menu is displayed see figure with the available options SET Access to the setup menu CMD Access to the commands menu PAS Password ...

Page 9: ...ave the parameters The device will reboot If no buttons are pressed for two minutes the setup menu is abandoned automatically and the system returns to the standard display without saving the parameters Remember that solely for the data that can be edited using the buttons a backup copy can be made in the DME D305T2MID s EEPROM If required this data can be restored to the working memory The backup...

Page 10: ... P04 02 Power integration time min 15 1 60 P04 03 Current integration time min 15 1 60 P04 04 Voltage integration time min 1 1 60 P04 05 Frequency integration time min 1 1 60 M05 HOUR COUNTER UoM Default Range P05 01 Hour counters general enable ON OFF ON P05 02 Partial hour counter 1 enable ON OFF ON LIMx P05 03 Hour counter 1 channel number x 1 1 4 P05 04 Partial hour counter 2 enable ON OFF ON ...

Page 11: ...8 n 06 P08 n 07 P08 n 08 as above with reference to the lower threshold P08 n 09 Permits inversion of the status of limit threshold LIMn P08 n 10 Defines whether the threshold is stored and must be reset manually ON or is reset automatically OFF Note this menu is divided into 4 sections for alarms ALA1 4 P09 n 01 Signal that causes the alarm It can be when a threshold LIMx is exceeded P09 n 02 Cha...

Page 12: ... In order to run the test the energy meter must be connected to an active system with the following conditions Three phase system with all phases present V 187VAC PH N Minimum current flow in each phase 1 of the CT full scale set Positive flow of energies i e a normal system where the inductive load draws power from the supply To launch the test execution enter the commands menu and select command...

Page 13: ...I509 GB I 09 17 31100345 G B 13 TERMINALS ARRANGEMENT AND MECHANICAL DIMENSIONS mm 90 71 6 104 7 58 45 Ø4 2 5 43 7 98 3 S1 S2 I1 I2 S2 S1 S1 S2 I3 T1 T2 SG B A TR V2 V1 V3 VN ...

Page 14: ...surement and tariff power supply circuit connection Type of terminal Screw type fixed Number of terminals 4 for supply measurement 2 for tariff selection input Cable cross section min max 0 2 4 0mm 24 12 AWG Tightening torque 0 8Nm 7 lbin Current input and static output connections Type of terminal Screw type fixed Number of terminals 6 for CT connections Cable cross section min max 0 2 2 5mm 24 1...

Page 15: ... und vom Bediener leicht zugänglich sein Er muss als Trennvorrichtung für das Gerät gekennzeichnet sein IEC EN 61010 1 6 11 2 Das Gerät mit einem weichen Tuch reinigen keine Scheuermittel Flüssigreiniger oder Lösungsmittel verwenden ADVERTENCIA Leer atentamente el manual antes de instalar y utilizar el regulador Este dispositivo debe ser instalado por personal cualificado conforme a la normativa d...

Page 16: ...are 4U 72mm per guida DIN Display LCD retroilluminato 2 uscite statiche Ingresso di tariffazione in AC 3 tasti di navigazione per funzioni ed impostazioni LED metrologico per indicazione flusso di energia Elevata accuratezza delle misure in vero valore efficace TRMS Misura energia attiva conforme a EN50470 3 classe B Contatori di energia attiva e reattiva totali e per singola fase Contatori di ene...

Page 17: ... I tasti e consentono di scorrere le pagine di visualizzazione misure una per volta La pagina attuale è riconoscibile tramite la visualizzazione della unità di misura nella parte alta del display Alcune delle misure potrebbero non essere visualizzate in funzione della programmazione e del collegamento dell apparecchio ad esempio se programmato per un sistema senza neutro le misure riferite al neut...

Page 18: ...ONTATORI DI ENERGIA L3 kWh L3 PAR SYS TAR 1 TAR 2 kWh L3 TOT 13 CONTATORI DI ENERGIA L1 kvarh L1 PAR SYS TAR 1 TAR 2 kvarh L1 TOT 14 CONTATORI DI ENERGIA L2 kvarh L2 PAR SYS TAR 1 TAR 2 kvarh L2 TOT 15 CONTATORI DI ENERGIA L3 kvarh L3 PAR SYS TAR 1 TAR 2 kvarh L3 TOT 16 CONTATORI DI ENERGIA L1 kvarh L1 PAR SYS TAR 1 TAR 2 kvarh L1 TOT 17 CONTATORI DI ENERGIA L2 kvarh L2 PAR SYS TAR 1 TAR 2 kvarh L...

Page 19: ...CA TENSIONI L N THD V L1 THD V L2 THD V L3 HI LO AV 36 DIST ARMONICA CORRENTE THD I L1 THD I L2 THD I L3 HI LO AV 37 CONTAORE hhhhhh mm ss TOT PAR 1 PAR 2 PAR 3 PAR 4 38 LIMITI LIM1 LIM2 LIM3 LIM4 39 ALLARMI ALA1 ALA2 ALA3 ALA4 40 TARIFFA SELEZIONATA tAr 1 e tAr 2 41 INFO REVISIONI SERIAL NR MODELLO REV SW Nr SERIE NOTA Le pagine evidenziate con colore grigio nella tabella sopra potrebbero non ess...

Page 20: ...ore massimo Valore minimo Valore medio Valore istantaneo Valore massimo Valore minimo Valore medio Valore istantaneo Valore massimo Valore minimo Valore medio Valore istantaneo Valore Max Demand Valore massimo Valore minimo Valore medio Tensioni di fase Correnti di fase e neutro Potenza attiva di fase e totale ...

Page 21: ...a il DME D305T2MID ha la possibilità di gestire 2 tariffe indipendenti oltre alla totale e alla parziale La selezione delle tariffe avviene normalmente tramite l ingresso digitale oppure in opzione tramite l invio di messaggi sul protocollo di comunicazione Per selezionare le 2 tariffe è disponibile la funzione di ingresso TAR A La sua attivazione effettua la selezione come da tabella L apparecchi...

Page 22: ...ce se può essere automatico allo scomparire delle condizioni di allarme o se necessita di un azzeramento manuale tramite menu comandi C 07 MENU PRINCIPALE Per accedere al menu principale Premere contemporaneamente e Viene visualizzato il menu principale vedi figura con le possibili scelte SET Accesso al menu impostazioni Setup CMD Accesso al menu comandi PAS Inserimento della password La scelta se...

Page 23: ...r uscire dalla impostazione e salvare i parametri L apparecchio si reinizializza Se non vengono premuti tasti per 2 minuti consecutivi il menu setup viene abbandonato automaticamente e il sistema torna alla visualizzazione normale senza salvare i parametri Rammentiamo che per i soli dati di setup modificabili da tastiera è possibile fare una copia di sicurezza backup nella memoria eeprom del DME D...

Page 24: ...ault Range P04 01 Modo integrazione Scorr Fisso Scorrevole Bus P04 02 Tempo integrazione potenze min 15 1 60 P04 03 Tempo integrazione correnti min 15 1 60 P04 04 Tempo di integrazione tensioni min 1 1 60 P04 05 Tempo di integrazione frequenza min 1 1 60 M05 CONTAORE UdM Default Range P05 01 Abilitazione generale contaore ON OFF ON P05 02 Abilitazione contaore parziale 1 ON OFF ON LIMx P05 03 Nume...

Page 25: ...pra riferiti alla soglia inferiore P08 n 09 Permette di invertire lo stato del limite LIMn P08 n 10 Definisce se la soglia rimane memorizzata e va azzerata manualmente ON o se si ripristina automaticamente OFF Nota questo menu è diviso in 4 sezioni per gli allarmi ALA1 4 P09 n 01 Segnale che provoca l allarme Può essere il superamento di una soglia LIMx P09 n 02 Numero del canale x riferito al par...

Page 26: ... contatore di energia è stata effettuata correttamente Per poter eseguire il test il contatore di energia deve essere inserito in un impianto attivo con le seguenti condizioni sistema trifase con presenza di tutte le fasi V 187VAC L N corrente minima circolante su ciascuna fase 1 del fondo scala del TA impostato verso positivo delle energie cioè in un comune impianto dove il carico induttivo assor...

Page 27: ...I509 GB I 09 17 31100345 I 27 DISPOSIZIONE MORSETTI E DIMENSIONI MECCANICHE mm 90 71 6 104 7 58 45 Ø4 2 5 43 7 98 3 S1 S2 I1 I2 S2 S1 S1 S2 I3 T1 T2 SG B A TR V2 V1 V3 VN ...

Page 28: ...d esercizio 4kV Connessioni circuito alimentazione misura e tariffa Tipo di morsetti A vite fissi Numero di morsetti 4 per alimentazione misura 2 per ingresso selezione tariffa Sezione conduttori min max 0 2 4 0mm 24 12 AWG Coppia di serraggio morsetti 0 8Nm 7lbin Connessioni ingressi corrente Tipo di morsetti A vite fissi Numero di morsetti 6 per connessioni TA Sezione conduttori min max 0 2 2 5 ...

Reviews: