TROUBLESHOOTING
SERVICE MANUAL – ALPHA SL 65S
AL017
Memory error
Clearing Method
Turn ARST (DI signal) ON to clear the fault or restart the servo drive.
Potential Cause
Checking Method
Corrective Actions
Parameter data error when
writing into EE- PROM.
Examine the parameter settings. Please do
the following steps:
1.Press SHIFT key on the drive keypad, and
examine the parameter shown on LED
display.
2.If E320A is displayed (in
hexadecimal format), it indicates it is
parameter P2-10. Please examine the
parameter settings of P2-10.
3.If E3610 is displayed (in hexadecimal
format), it indicates it is parameter
P6-16. Please examine the parameter
settings of P6-16.
1.If this fault occurs when
power is applied to the drive, it
indicates that the setting value
of one
parameter has exceeded the
specified range. Correct the
setting value of the parameter
to clear the fault and restart the
servo drive.
2.If this fault occurs during
normal operation, it indicates
that the error occurs when
writing data
into EE-PROM. Turn ARST (DI
signal) ON to clear the fault or
restart the servo drive.
The setting value of hidden
parameter is in error.
Press SHIFT key on the drive keypad and
examine if E100X is displayed on LED
display.
If this fault occurs when
resetting the parameter
settings, it indicates that the
servo drive type is not set
correctly. Correctly set the
servo drive type again.
Data in EE-PROM is
damaged.
Press SHIFT key on the drive keypad and
examine if E0001 is displayed on LED
display.
If this fault occurs when power
is applied to the drive, it
indicates that the data in EE-
RPM is damaged or there is no
data in EE-PROM. Please
contact your distributor for
assistance or contact with
Delta.
AL018
Encoder output error
Clearing Method
Turn ARST (DI signal) ON to clear the fault.
Potential Cause
Checking Method
Corrective Actions
Encoder itself or the wiring
of encoder is in error.
Check if the recent fault records (P4-
00 ~ P4-05) display on the drive keypad in
accordance with the fault codes AL011,
AL024, AL025 and AL026.
Perform the corrective actions
as described in AL011, AL024,
AL025 and AL026.
The output frequency for
pulse output may exceed
the limit of its allowable
setting value.
Check if the following conditions occur:
Condition 1: Motor speed is above the value
set by P1-76.
Condition 2:
Correctly set P1-76 andP1-46.
Ensure that the motor speed is
below the value set by P1-76.
Summary of Contents for ALPHA SL65 S
Page 5: ...GENERAL SERVICE MANUAL ALPHA SL 65S...
Page 29: ...PROCEDURES SERVICE MANUAL ALPHA SL 65S...
Page 37: ...MECHANICAL EQUIPMENT SERVICE MANUAL ALPHA SL 65S...
Page 41: ...PNEUMATIC EQUIPMENT SERVICE MANUAL ALPHA SL 65S...
Page 59: ...ELECTRICAL EQUIPMENT SERVICE MANUAL ALPHA SL 65S...
Page 87: ...MAINTENANCE SERVICE MANUAL ALPHA SL 65S...
Page 89: ...TECHNICAL CHARACTERISTICS SERVICE MANUAL ALPHA SL 65S...
Page 91: ...DISPOSAL SERVICE MANUAL ALPHA SL 65S...
Page 101: ...TROUBLESHOOTING SERVICE MANUAL ALPHA SL 65S SEQUENCE LISTING...
Page 102: ...TROUBLESHOOTING SERVICE MANUAL ALPHA SL 65S...
Page 116: ...TROUBLESHOOTING SERVICE MANUAL ALPHA SL 65S PLC INPUTS OUTPUTS...
Page 117: ...TROUBLESHOOTING SERVICE MANUAL ALPHA SL 65S...
Page 121: ...TROUBLESHOOTING 121 SERVICE MANUAL ALPHA SL 65S...
Page 123: ...APPENDICES 123 SERVICE MANUAL ALPHA SL 65S WIRING DIAGRAM BSL65 A8...
Page 124: ...124 APPENDICES SERVICE MANUAL ALPHA SL 65S...
Page 125: ...APPENDICES 125 SERVICE MANUAL ALPHA SL 65S...
Page 126: ...126 APPENDICES SERVICE MANUAL ALPHA SL 65S...
Page 127: ...APPENDICES 127 SERVICE MANUAL ALPHA SL 65S...
Page 128: ...128 APPENDICES SERVICE MANUAL ALPHA SL 65S PNEUMATIC DIAGRAM...