Assembly instructions | LK Electronic Thermostat TR 26

Technical data

LK Electronic Thermostat TR 26

Article no.

241 81 48

Temperature range 

+0 – +60 C° 

∆t adjustment 

0,5 – 5 K 

Power loss 

2,5 VA 

Operating voltage 

230 V AC 

Change-over contact, 

volt free 

24/230 V AC 

Max. load 

8 (2) A, 250 V AC 

Insulation class 

IP20

Assembly 

DIN EN 60715 mounting for 

rail

Dimensions 

35 x 90 x 76,5 mm 

Energy declaration in accordance with  
EU 811/2013. 

Temperature regulator class

I

Temperature regulator’s contribution to 

seasonal space heating energy efficiency

1%

90,0

45,0

35,0

58,0

76,5

53,0

LK Cable Sensor FK 133/4

Article no 

241 81 49 

Sensor element 

KTY semi-conductor 

Sensor cable 

PVC 2 x 0.5 mm² 

Length 

4 m 

Diameter/length of  

sensor section 

6 x 43 mm 

85,00 ± 5 
55,00 ± 2 

 

LIYY 2 x 0,5

4,0 m (length)

±5 

35 

Ø6,0    ±0,1 

43 

±1,5 

Cable size when extending

Cable size when extending sensor cable for 
FK133/4 and cable size for connection of FS 103.

30 m 

2 x 0,50 mm² 

45 m 

2 x 0,75 mm² 

60 m 

2 x 1,00 mm² 

90 m 

2 x 1,50 mm² 

Ohm table

Ohm table for sensor FK133/4 and FS 103.

-5 °C 

1525 Ohm 

0 °C 

1592 Ohm 

+5 °C 

1661 Ohm 

+10 °C 

1732 Ohm 

+15 °C 

1805 Ohm 

+20 °C 

1879 Ohm 

+25 °C 

1956 Ohm 

+30 °C 

2035 Ohm 

+35 °C 

2115 Ohm 

+40 °C 

2197 Ohm 

+45 °C 

2282 Ohm 

+50 °C 

2368 Ohm 

+55 °C 

2456 Ohm 

+60 °C 

2546 Ohm 

+65 °C 

2638 Ohm 

Connection of sensors for average 

temperature regulation

1 Sensor

4 Sensors

9 Sensors