4 3 2 Compliance and Safety Symbols
. .
Electrical
shock!
There are residual voltages in the PV inverter It needs 5 minutes
.
to finish discharge
.
5mins
The PV inverter must not be touched when in operation Its
.
enclosure and heat sinks are extremely hot
.
Electrical shock! This part is charged Only qualified and/or trained
.
electrical technicians are allowed to perform operations on the inverter
.
If the inverter service life has expired dispose it in accordance with
,
local rules for disposal of electrical equipment waste Do not dispose
.
the PV inverter with household garbage
.
The PV inverter is compliant with TUV
.
Safety symbol
Description
Applies to wall-mounting installation, as described below in detail.
Basic Requirements
a
The inverter is protected to IP65 and can be installed indoors or outdoors
.
.
b
The installation method and position must be appropriate for the weight and dimensions of
.
the inverter.
c
Do not install the inverter in a place where personnel are likely to come into contact with its
.
enclosure and heat sinks because these parts are extremely hot during operation.
d
Do not install the inverter in an area that stores flammable or explosive materials
.
.
a
The ambient temperature must be below 50
which ensures the inverter
’
s optimal
.
℃
operation and extends its service life.
Installation Environment Requirements
4 4 1 Determining the Installation Position
. .
4 4 Installation Requirements
.