The Power Prowler determines the length of a variety of cable types and
calculates the VOP of a cable with known length.
When connecting to a cable, use proper adapters for the application.
When connecting to energized cables over 60V, you will need the leader
cable (CA008) rated at 600V CAT III. If a leader cable is being used, the
leader installed
option
should be selected for a more
accurate length reading. See Setting Options for more information on
leader settings (page 9).
Internal Power Prowler components are protected to 600V peak
AC or DC. Connecting the unit to cabling with voltages above 600V
peak AC or DC may damage the unit and pose a safety hazard for
the user.
To Begin a Fault Location Test
▪
Press the red
Power
button
to turn the unit on.
▪
Connect the proper adapter for your application to the Power Prowler,
and then connect to the cable under test. Select the Fault Location
icon by pressing the
Left/Right
buttons, then press the
Enter
button
or press the
Fault Location
soft key
.
▪
Use the
Left/Right
buttons to scroll to the cable type being tested.
The cable type appears on the bottom of the screen.
▪
Press the
Test
button
to measure the length of the cable or the
distance to a fault.
FAULT LOCATION (ssTDR OPERATION)