Littlefuse Startco SE-134C Manual Download Page 3

 

 

Page 1 

 

SE-134C Ground-Fault Ground-Check Monitor

 Rev. 

 
 

Pub. SE-134C-M, December 16, 2009. 

1.  G

ENERAL

 

  The SE-134C is a microprocessor-based, combination 
ground-fault and ground-wire monitor for resistance-
grounded systems.  It has a switching power supply that 
accepts a wide range of ac and dc voltages, its 
specifications apply over an industrial temperature range 
at high humidity, and it meets the IEEE surge-withstand-
capability tests (oscillatory and fast transient) for 
protective relays and relay systems.  Isolated, normally 
open and normally closed contacts are provided for 
contactor control or for shunt or undervoltage operation 
in a breaker-trip circuit.  All operating conditions are 
clearly annunciated and two Form C contacts are 
provided for remote indication.  The SE-134C is housed 
in an anodized extruded-aluminum enclosure, and all 
connections are made with plug-in, wire-clamping 
terminal blocks.  Provision is made for both panel and 
surface mounting. 
 The ground-fault circuit detects fundamental-
frequency, zero-sequence current with a window-type 
current sensor and it verifies that the current sensor is 
connected and not shorted.  A definite-time characteristic 
with 11 trip levels and 11 trip times allows coordination 
in virtually any resistance-grounded system.  Although 
other current sensors may satisfy the verification circuit, 
only SE-CS10-series sensors have characteristics that 
meet system specifications.  Current-sensor verification 
can be disabled for a ground-check-only application. 
  The ground-check circuit has an open-circuit voltage of 
24 Vdc, which is not a hazard to personnel, and it has an 
output drive current above 100 

mA for optimum 

performance in slip-ring, commutated-load, and high-
induced-ac applications.  Features include an externally 
accessible ground-check fuse, a resistance-insertion test, 
3-kV isolation between the ground-check loop and the 
monitor electronics, and a PPI-600V accessory for 
parallel-ground-path rejection.  A PPI-600V will also 
eliminate intermachine arcing and prevent stray ac and dc 
currents from flowing in the monitored ground wire.  
Unlike ground-check circuits using other termination 
devices, and especially those with phase-reversal 
switches, a ground-check circuit using a termination 
device with a Zener characteristic is capable of loop 
measurements that are independent of current in the phase 
conductors.  The SE-134C ground-check circuit 
recognizes the SE-TA6A-series 5.6-volt Zener 
characteristic as a valid end-of-line completion.  This is 
the only passive characteristic that will satisfy the ground-
check circuit’s multi-level drive, allow induced currents 
to circulate in the ground-check loop, survive a phase-to-
ground-check fault, and clamp the ground-check voltage 
during the fault.  Although a standard 5.6-volt Zener 
diode may engage the SE-134C’s ground-check circuit, 
only an SE-TA6A-series termination assembly has the 
compensation required to meet system specifications.  In 

select applications, a combination of an SE-TA12A and 
SE-TA12B Termination Assemblies can be used to 
monitor the cables of a splitter box (junction box) using a 
single SE-134C Monitor.  See Technical Note GC-11, 
available at www.startco.ca. 
 

2.  O

PERATION

 

2.1  G

ROUND

-F

AULT

 C

IRCUIT 

2.1.1  GF

 

T

RIP 

T

IME 

S

ETTING

 

 The ground-fault circuit has a definite-time 
characteristic with 11 settings from 0.1 to 2.5 seconds.  
Time-coordinated ground-fault protection requires the trip 
time to be longer than the trip time of downstream 
ground-fault devices.   
 

2.1.2  GF

 

T

RIP 

L

EVEL 

S

ETTING 

  The trip level of the ground-fault circuit is switch 
selectable with 11 settings from 0.5 to 12.5 A.  A 
minimum tripping ratio of 5 is recommended to achieve at 
least 80% winding protection, and this requires the trip 
level to be less than 20% of the grounding resistor let-
through current.  Suggested trip-level ranges for 5-, 15-, 
and 25-A neutral-grounding resistors are indicated on the 
faceplate.  A ground-fault trip is latched, requiring a reset.  
A current-sensor failure will also cause a ground-fault 
trip.  See Section 3.1 
   If the SE-134C is operated in a ground-check-only 
application and an SE-CS10 is not connected, connect 
terminals 17 and 18 to disable sensor verification.  See 
Fig. 1. 
 

2.2  G

ROUND

-C

HECK

 C

IRCUIT 

 

The ground-check loop consists of the outgoing 

ground-check conductor, quick-coupler connections, the 
SE-TA6A-series termination assembly, the SE-TA6A 
connection to equipment frame or ground bus, the 
ground-return path, and the SE-134C cable-ground-
terminal connection to substation ground. 
  The SE-134C detects a valid ground-check loop when 
an SE-TA6A-series termination assembly is detected in 
the loop and loop resistance is less than 28 ohms.  The 
loop is not valid if open (or high resistance), or if the 
ground-check conductor is shorted to ground. 
  When the ground-check loop is valid, the SE-134C 
ground-check circuit can be tested by pressing the GC 
TEST switch or by shorting GC TEST terminals 11 and 
12.  This test invalidates the loop by inserting 47 

Ω

 in the 

ground-check loop and a trip should occur in less than 
250 ms.  
  The ground-check circuit is usually operated in the 
non-latching mode; however, it can be operated in the 
latching mode by connecting terminals 14 and 15.   
  The ground-check circuit is protected by a 1.5-A time-
delay fuse (F1). 

Summary of Contents for SE-134C

Page 1: ...F TRIP LEVEL A GF TRIP TIME S POWER DIAGNOSTIC ERROR 10 50 20 75 30 1 0 40 1 5 50 2 0 70 2 5 1 0 1 3 5 0 1 6 7 5 2 0 10 0 2 5 12 5 G C T E S T R E S E T SHORT OPEN VALID TRIP GROUND CHECK SENSOR TRIP GROUND FAULT 3 0 SHORT OPEN VALID TRIP GROUND CHECK 5 A N G R 5 A N G R 15 R A NG 15 R A NG 25 A NGR 25 A NGR S E 1 3 4 C Copyright 2009 by Littelfuse Startco All rights reserved Publication SE 134C M...

Page 2: ...est 14 8 1 2 Non Latching Ground Check Trip Test 14 8 2 Trip Relay Fail Safe Mode Test 14 8 3 Current Sensor Verification Test 14 8 4 SE TA6A Series Termination Assembly Tests 15 8 5 Ground Fault Performance Test 15 LIST OF FIGURES FIGURE PAGE 1 SE 134C Typical Application 4 2 SE 134C Outline and Panel Mounting Details 5 3 SE 134C Outline and Surface Mounting Details 6 4 SE CS10 Current Sensors 7 ...

Page 3: ...ristic that will satisfy the ground check circuit s multi level drive allow induced currents to circulate in the ground check loop survive a phase to ground check fault and clamp the ground check voltage during the fault Although a standard 5 6 volt Zener diode may engage the SE 134C s ground check circuit only an SE TA6A series termination assembly has the compensation required to meet system spe...

Page 4: ...ip circuits are not fail safe and are not recommended because Shunt trip devices do not operate if supply voltage fails Shunt trip ground check circuits allow the power circuit and open cable couplers to be energized for a short interval after supply voltage is applied CAUTION The SE 134C is not a lock out device Follow lock out procedures for maintenance 3 INDICATION 3 1 GROUND FAULT A red LED in...

Page 5: ... Outline dimensions and mounting details for the SE CS10 series current sensors are shown in Fig 4 Pass only phase conductors through the sensor window as shown in Fig 1 If a shield ground or ground check conductor enters the sensor window it must be returned through the window before it is terminated Connect the current sensor to terminals 16 and 17 Ground terminal 17 Current sensor primary and s...

Page 6: ...CT 17 18 TO DISABLE SENSOR VERIFICATION CABLE GROUND GC INDICATOR GF INDICATOR GC G SE TA6A GC G SE TA6A 13 14 15 CONNECT 12 13 FOR NON FAIL SAFE OPERATION OF THE TRIP RELAY CONNECT 14 15 FOR LATCHING GROUND CHECK NFS GROUND CHECK LATCH DISABLE SENSOR VERIFICATION R G NOTES 1 RELAY CONTACTS SHOWN WITH SE 134C DE ENERGIZED TERMINALS 3 4 5 6 AND 7 8 ARE INTERNALLY CONNECTED THE RK 132 REMOTE INDICAT...

Page 7: ... 8 CABLE GROUND 9 10 1 1 12 13 14 15 16 17 18 RESET GC TEST NFS GC LATCH CURRENT SENSOR DISABLE SENSOR VERIFICATION 1 9 20 2 1 22 23 24 25 26 27 28 GF GC TRIP B TRIP A FUSE F1 1 5 A 500 VAC TIME DELAY F1 FRONT VIEW 98 3 3 87 212 6 8 37 G R O U N D F A U L T G R O U N D C H E C K M O N I T O R GF TRIP LEVEL A GF TRIP TIME S POWER DIAGNOSTIC ERROR 10 50 20 75 30 1 0 40 1 5 50 2 0 70 2 5 1 0 1 3 5 0 ...

Page 8: ...O U N D F A U L T G R O U N D C H E C K M O N I T O R GF TRIP LEVEL A GF TRIP TIME S POWER DIAGNOSTIC ERROR 10 50 20 75 30 1 0 40 1 5 50 2 0 70 2 5 1 0 1 3 5 0 1 6 7 5 2 0 10 0 2 5 12 5 G C T E S T R E S E T SHORT OPEN VALID TRIP GROUND CHECK SENSOR TRIP GROUND FAULT 3 0 SHORT OPEN VALID TRIP GROUND CHECK 5 A N G R 5 A N G R 15 R A NG 15 R A NG 25 A NGR 25 A NGR 98 3 152 0 114 3 8 0 3 87 5 98 4 50...

Page 9: ... 0 9 00 279 4 11 00 169 9 6 69 215 9 8 50 266 7 10 50 77 2 3 04 101 6 4 00 108 7 4 28 32 5 1 28 31 8 1 25 38 9 1 53 123 7 4 87 165 0 6 50 225 0 8 86 60 5 2 38 73 2 2 88 80 0 3 15 M4 8 32 M10 0 375 M10 0 375 H1 X1 TERMINAL LOCATION MAY VARY SE CS10 2 5 63 5 2 50 135 1 5 32 124 0 4 88 72 6 2 86 27 9 1 10 69 9 2 75 54 4 2 14 M4 8 32 I 138 2 5 44 171 5 6 75 200 7 7 90 88 9 3 50 J 138 2 5 44 171 5 6 75...

Page 10: ... 800 TEC FUSE 1 800 832 3873 Made in Saskatoon Canada Rating 5 6 Vdc 105 mA 50 W Max Use with Ground Fault Ground Check Monitor Models SE 134 and SE 134C R 8 0 0 31 LR 53428 US C R Revision SE TA6A WL TERMINATION ASSEMBLY Serial Number 00 00000000 1 800 TEC FUSE 1 800 832 3873 Made in Saskatoon Canada Rating 5 6 Vdc 105 mA 50 W Max Use with Ground Fault Ground Check Monitor Models SE 134 and SE 13...

Page 11: ...1 800 TEC FUSE 1 800 832 3873 Made in Saskatoon Canada TERMINATION ASSEMBLY FIGURE 6 SE TA6ASF WL Small Format Termination Assembly NOTES 1 ONE RED AND ONE GREEN LED LIGHT 24 120 VAC DC NOT POLARITY SENSITIVE 2 YELLOW PUSH BUTTON 3 A 240 VAC A600 0 5 A 125 VDC Q600 3 DIMENSIONS IN MILLIMETRES INCHES 4 INDICATES CLEARANCE REQUIRED 5 PANEL THICKNESS 1 0 TO 6 0 0 04 TO 0 24 6 NEMA 4X LEGEND PLATE 30 ...

Page 12: ...Page 10 SE 134C Ground Fault Ground Check Monitor Rev 2 Pub SE 134C M December 16 2009 FIGURE 8 PPI 600V Parallel Path Isolator ...

Page 13: ...HE FLANGE IS ISOLATED FROM THE GROUND PIN AND USE A MATING PLUG WITH A NON METALLIC HOUSING OR ISOLATE THE FLANGE FROM THE CHASSIS IF THE MATING PLUG HAS A METALLIC HOUSING 3 CABLE PLUGS AND RECEPTACLES WITH GROUNDED METAL HOUSINGS MUST BE ISOLATED FROM EARTH TO PREVENT PARALLEL GROUND PATHS OUTGOING OUTGOING GROUND CHECK GROUND GC G PPI 600V CHASSIS GROUND BUS CABLE GROUND G GROUND CHECK GC GROUN...

Page 14: ...ng Mode Latching or Non Latching Trip Relay CSA UL Contact Rating 8 A Resistive 250 Vac 5 A 30 Vdc HP B300 Pilot Duty Supplemental Contact Ratings Make Carry 0 2 s 30 A Break dc 75 W Resistive 35 W Inductive L R 0 04 Break ac 2 000 VA Resistive 1 500 VA Inductive PF 0 4 Subject to maximums of 8 A and 250 V ac or dc Contact Configuration Isolated N O and N C Contacts Operating Mode Fail Safe or Non...

Page 15: ...m 14 Dimensions 105 x 40 x 22 2 mm 4 13 x 1 57 x 0 87 Shipping Weight 300 g 0 7 lb SE TA6ASF WL Characteristic 5 6 V Zener Temperature Compensated Power Rating 12 W Wire Leads 18 AWG 300 mm 11 8 Dimensions 58 8 x 19 x 12 7 mm 2 32 x 0 75 x 0 5 Shipping Weight 45 g 0 1 lb Certification CSA Canada and USA LR 53428 US C R 6 ORDERING INFORMATION SE 134C Future Options Power Supply 0 Universal ac dc Su...

Page 16: ...nd the SHORT LED will be flashing The TRIP contacts terminals 22 23 and 24 25 will remain latched and ground check indication contacts terminals 26 27 and 26 28 will change state Reset the monitor 8 1 2 NON LATCHING GROUND CHECK TRIP TEST Connect the monitor current sensor and termination device as shown in Fig 10 With supply voltage applied the POWER SENSOR and VALID LED s will be on Open the gro...

Page 17: ...uipment manufacturer s detailed instructions b Verify proper location of the ground fault current transformer Ensure the cables pass through the ground fault current transformer window This check can be done visually with knowledge of the circuit The connection of the current transformer secondary to the SE 134C is not polarity sensitive c Verify that the system is correctly grounded and that alte...

Page 18: ...R GROUND FAULT RELAY TEST UNIT SE 100T or SE 400 NOTES 1 MOMENTARILY CONNECT 9 10 TO PERFORM REMOTE RESET 2 MOMENTARILY CONNECT 11 12 TO PERFORM REMOTE GROUND CHECK TEST 3 CONNECT 12 13 FOR NON FAIL SAFE OPERATION OF THE TRIP RELAY 4 CONNECT 14 15 FOR LATCHING GROUND CHECK TRIP 5 CONNECT 17 18 TO DISABLE CURRENT SENSOR VERIFICATION 6 CONTACTS SHOWN DE ENERGIZED 7 REMOVE TERMINAL 3 CONNECTION WHEN ...

Reviews: