Page 13
SE-134C Ground-Fault Ground-Check Monitor
Rev.
1
Pub. SE-134C-M, December 16, 2009.
5.2 C
URRENT
S
ENSORS
SE-CS10-2.5:
Current Ratio ...................... 1,000:5 A
Insulation
............................
600-V
Class
Window Diameter .............. 63 mm (2.5”)
Shipping Weight ................ 690 g (1.5 lb)
SE-CS10-4:
Current Ratio ...................... 1,000:5 A
Insulation
............................
600-V
Class
Window Diameter .............. 108 mm (4.2”)
Shipping Weight ................ 1.9 kg (4.3 lb)
SE-CS10-6:
Current Ratio ...................... 1,000:5 A
Insulation
............................
600-V
Class
Window Diameter .............. 160 mm (6.3”)
Shipping Weight ................ 2.2 kg (4.8 lb)
SE-CS10-8:
Current Ratio ...................... 1,000:5 A
Insulation
............................
600-V
Class
Window Diameter .............. 209 mm (8.2”)
Shipping Weight ................ 2.2 g (4.8 lb)
5.3 T
ERMINATION
A
SSEMBLIES
SE-TA6A:
Characteristic ..................... 5.6-V Zener, Temperature
Compensated
Power Rating ...................... 50 W
Screw Terminal .................. 6-32 x 0.25
Dimensions
.........................
105 x 40 x 41.5 mm
(4.13 x 1.57 x 1.63”)
Shipping Weight ................ 300 g (0.7 lb)
SE-TA6A-WL
Characteristic ..................... 5.6-V Zener, Temperature
Compensated
Power Rating ...................... 50 W
Wire Leads ......................... 14 AWG, 356 mm (14”)
Dimensions
.........................
105 x 40 x 22.2 mm
(4.13 x 1.57 x 0.87”)
Shipping Weight ................ 300 g (0.7 lb)
SE-TA6ASF-WL:
Characteristic ..................... 5.6-V Zener, Temperature
Compensated
Power Rating ..................... 12 W
Wire Leads ......................... 18 AWG, 300 mm (11.8”)
Dimensions ........................ 58.8 x 19 x 12.7 mm
(2.32 x 0.75 x 0.5”)
Shipping Weight ................ 45 g (0.1 lb)
Certification .............................. CSA Canada and USA
LR 53428
US
C
R
6. O
RDERING
I
NFORMATION
SE-134C-
Future Options
Power Supply:
0
Universal ac/dc Supply
1
24 to 48-Vdc Supply
SE-134C ............................Ground-Fault Ground-Check
Monitor complete with
SE-134-SMA
Surface-Mount
Adapter
Ground-Check Termination:
SE-TA6A ...................50-W Standard Termination
Assembly
SE-TA6A-WL............50-W Termination Assembly
with
Wire
Leads
SE-TA6ASF-WL
.......12-W
Small-Format
Termination
Assembly with Wire Leads
Current Sensors:
SE-CS10-2.5 ..............Current Sensor,
63 mm (2.5”) Window
SE-CS10-4 .................Current Sensor,
108 mm (4.2”) Window
SE-CS10-6 .................Current Sensor,
160 mm (6.3”) Window
SE-CS10-8 .................Current Sensor,
209 mm (8.2”) Window
Parallel Path Isolator
PPI-600V ...................For system voltages up to
600
Vac
Accessories:
RK-132
......................Remote
Indication and Reset,
Includes two 120-V pilot
lights, a reset push button, and
legend plates