PGR-6101 Ground-Fault & Insulation Monitor
Page 4
Rev. 0-C-041918
3.1 PGH-5000
AND
PGH-6000
For
5-kV
and
6-kV
systems,
connect
the
PGR-6101 to the monitored circuit with a PGH-5000 and
PGH-6000
respectively.
See
Fig.
4
for
PGH-5000 outline and mounting details. See Fig. 5 for
PGH-6000 outline and mounting details.
Connect protective-ground terminal (
) to ground.
Connect
terminal
E
to
ground
or
to
PGR-6101 terminal 30, which must be grounded.
Connect terminal M to PGR-6101 terminal 29.
(PGR-6101 terminal 2 is not used.) For PGR-6101 to
PGH-5000/PGH-6000
distances
greater
than
10 m (30’), use shielded cable, and connect the cable
shield to the second PGH-5000/PGH-6000 terminal E.
Connect terminal A to one phase on the load side of the
motor starter. See Fig. 2. The PGH-5000/PHG-6000
includes 915 mm (36”) of high-voltage conductor.
FIGURE 2. Typical Connection Diagram.