Littelfuse PGR-6101 Manual Download Page 14

 

PGR-6101 Ground-Fault & Insulation Monitor 

 

Page 10 

 

 

Rev. 0-C-041918

 

 
 

 

 

FIGURE 7.  PGA-0510 Analog Ohm Meter. 

 

6.  P

ERFORMANCE 

T

ESTS 

6.1  G

ROUND-

F

AULT 

T

EST 

  Some  jurisdictions  require  periodic  ground-fault 
performance  tests.    A  test  record  form  is  provided  for 
recording the date and the result of the performance tests.  
The  following  ground-fault  system  tests  are  to  be 
conducted by qualified personnel. 

a)  Evaluate the interconnected system in accordance with 

the  overall  equipment  manufacturer’s  detailed 
instructions. 

b)  Verify  proper  location  of  the  PGC-5000-series  CT.  

Ensure the cables pass through the CT window.  This 
check  can  be  done  visually  with  knowledge  of  the 
circuit.    The  connection  of  the  current-sensor 
secondary to the PGR-6101 is not polarity sensitive. 

 
c)  Verify  that the system is  correctly grounded and that 

alternate  ground  paths  do  not  exist  that  bypass  the 
current  sensor.    High-voltage  testers  and  resistance 
bridges  can  be  used  to  determine  the  existence  of 
alternate ground paths. 

d)  Verify  proper  reaction  of  the  circuit-interrupting 

device in response to a simulated or controlled ground-
fault  current.    To  simulate  ground-fault  current,  use 
CT-primary  current  injection.    Fig.  8  shows  a  test 
circuit  using  the  SE-400  Ground-Fault-Relay  Test 
Unit.  The SE-400 has a programmable  output  of 0.5 
to 9.9 A  for a duration  of 0.1 to 9.9 seconds.  Fig.  8 
shows  the  use  of  resistors  that  reduce  the  injected 
current  to  10%  of  the  SE-400  setting.    Set  the  test 
current to 120%  of the PGR-6101 setting.   Inject the 
test  current  through  the  CT  window  for  at  least  2.5 
seconds.  Verify that the circuit under test has reacted 
properly.    Correct  any  problems  and  re-test  until  the 
proper reaction is verified. 

Summary of Contents for PGR-6101

Page 1: ...0 832 3873 E mail techline littelfuse com www littelfuse com PGR 6101 MANUAL GROUND FAULT INSULATION MONITOR Revision 0 C 041918 Copyright 2018 by Littelfuse Inc All rights reserved Document Number PM...

Page 2: ...PGR 6101 Ground Fault Insulation Monitor Page i Rev 0 C 041918 This page intentionally left blank...

Page 3: ...1 PGR 6101 8 4 1 1 PGR 6101 Online Operation 8 4 1 2 PGR 6101 Offline Operation 8 4 2 PGH High Tension Couplers 9 5 Ordering Information 9 6 Performance Tests 10 6 1 Ground Fault Test 10 6 2 Insulati...

Page 4: ...PGR 6101 Ground Fault Insulation Monitor Page iii Rev 0 C 041918 This page intentionally left blank...

Page 5: ...2 2 2 PGR 6101 OPERATING MODE Connect terminals 27 and 28 to a normally closed Form B auxiliary starter contact When terminals 27 and 28 are open Online mode insulation monitoring off is selected and...

Page 6: ...eutral side of the supply voltage and terminal 5 See Fig 2 For an alternate configuration connect a normally open double pole single throw switch across terminals 18 and 19 and terminals 21 and 22 A m...

Page 7: ...PGR 6101 Ground Fault Insulation Monitor Page 3 Rev 0 C 041918 FIGURE 1 PGR 6101 Outline and Mounting Details...

Page 8: ...ive ground terminal to ground Connect terminal E to ground or to PGR 6101 terminal 30 which must be grounded Connect terminal M to PGR 6101 terminal 29 PGR 6101 terminal 2 is not used For PGR 6101 to...

Page 9: ...PGR 6101 Ground Fault Insulation Monitor Page 5 Rev 0 C 041918 FIGURE 3 PGC 5000 Series Current Sensors...

Page 10: ...PGR 6101 Ground Fault Insulation Monitor Page 6 Rev 0 C 041918 FIGURE 4 PGH 5000 Outline and Mounting Details...

Page 11: ...PGR 6101 Ground Fault Insulation Monitor Page 7 Rev 0 C 041918 FIGURE 5 PGH 6000 Outline and Mounting Details...

Page 12: ...rail 115 mm 4 5 Shipping Weight 0 45 kg 1 lb Environment Operating Temperature 10 to 60 C 14 to 140 F Storage Temperature 40 to 80 C 40 to 176 F Humidity 85 Non Condensing Enclosure Rating IP20 Altitu...

Page 13: ...g 10 AWG 5 26 mm2 maximum High Tension Lead A 8 AWG 8 36 mm2 40 kVdc 915 mm 36 5 ORDERING INFORMATION PGA 0500 Analog Percent Current Meter PGA 0510 Analog Ohm Meter PGC 5025 Current Sensor 25 0 mm 0...

Page 14: ...sensitive c Verify that the system is correctly grounded and that alternate ground paths do not exist that bypass the current sensor High voltage testers and resistance bridges can be used to determin...

Page 15: ...etain this record for the authority having jurisdiction 6 2 INSULATION TEST Perform this test with the starter open and appropriate lock out procedures Connect a 10 k resistor between one phase and gr...

Page 16: ...2018 0 C 041918 01 February 6 2014 0 B 020614 November 22 2013 0 A 112213 00 MANUAL REVISION HISTORY REVISION 0 C 041918 SECTION 4 Specifications added REVISION 0 B 020614 SECTION 3 Fig 3 updated SECT...

Reviews: