READ AND FOLLOW ALL SAFETY INSTRUCTIONS
WIRING DIAGRAMS
REMOTE CAPABLE
BLUE(-)
)
BLUE(-)
BLUE(-)
)
LAMP
)
LAMP
READY
TEST
BATTERY
BLACK
Note:
Unused input lead must
be properly insulated with
wire nut or other approved
method.
RED
RED
BLACK
WHITE
277V
120V
0V
CHARGER
BOARD
LAMP
READY
TEST
BATTERY
RED
BLACK
RED
BLACK
WHITE
277V
120V
0V
LAMP
)
BLUE(-)
)
BLUE(-)
CHARGER
BOARD
AC INPUT CONNECTOR
(MOUNTING PLATE)
AC INPUT CONNECTOR
(MOUNTING PLATE)
TO REMOTE
Note for HO models:
Use 18-22 AWG stranded
wire to connect remote lamp
heads.
SAVE THESE INSTRUCTIONS
and deliver to owner after installation
PAGE:
3
of
4
Condition - Emergency lights are dim
1. Battery not fully charged. Allow battery to recharge for 24 hours and then retest. If lights are still dim, replace battery.
TROUBLESHOOTING:
Condition - The emergency lights do not operate
1. If the charge indicator light is OFF: Check that the circuit breaker for AC supply is ON.
2. If the charge indicator light is ON: Check that battery is properly connected. If problem persists, Replace battery. If remote lamps (where appli-
cable) are connected to the equipment, then turn OFF the AC supply and disconnect the remote circuit wires from the equipment. Turn ON the
AC supply and depress the test switch. If the local lamps (mounted on the equipment itself) come ON, then check the remote circuit for short or
overload condition and correct as required. Reconnect the circuit wires and restore AC power. If the local lamps don’t turn ON after disconnecting
the remote circuit wires, then replace battery.