Lithonia Lighting EU2C Installation Instructions Download Page 2

INSTALLATION INSTRUCTIONS for Lithonia Lighting EU2C Models

SAVE THESE INSTRUCTIONS 

and deliver to owner after installation

LED DUAL HEAD EMERGENCY LIGHTING FIXTURE

 READ AND FOLLOW ALL SAFETY INSTRUCTIONS 

WARNING:

 FAILURE TO FOLLOW THESE INSTRUCTIONS 

AND WARNINGS MAY RESULT IN DEATH, SERIOUS INJURY OR 
SIGNIFICANT PROPERTY DAMAGE. For your protection, read and 
follow these warnings and instructions carefully before installing or 
maintaining this equipment. These instructions do not attempt to cover 
all installation and maintenance situations. If you do not understand 
these instructions or additional information is required, contact 
LITHONIA LIGHTING or your local LITHONIA LIGHTING distributor.

WARNING: 

RISK OF ELECTRIC SHOCK - NEVER CONNECT 

TO, DISCONNECT FROM, OR SERVICE WHILE EQUIPMENT IS 
ENERGIZED.

WARNING:

 RISK OF FIRE. Lamps are hot. Keep combustible material away from hot parts. Observe lamp manufacturer’s warnings, 

recommendations and restrictions on lamp operation and maintenance. Make sure lamps are correctly installed.

CAUTION:

 The battery in this unit may not be fully charged. After electricity is connected to unit, let battery charge for at least 24 

hours, then normal operation of this unit should take effect. To check, press the TEST button. The lamps on the unit should turn on.

IMPORTANT SAFEGUARDS:

 When using electrical equipment, basic safety precautions should 

always be followed, including the following:

PAGE: 1 of 

4

Fig.A (J-Box)

Fig.B

Fig.C

BATTERY CONNECTOR

PLUG IN

NOTE

:

 

Complies

 with California Title 20

. P

roduct label is marked with

          .

INSTALLATION:

NOTE: 

Max mounting height 

is 

10

 ft to achieve at least 1 ft-candle of illuminance in emergency

 

mode.

Do not use outdoors.

Consult local building code for approved wiring and installation.

Disconnect AC power before servicing and installation.

Do not mount near gas or electric heaters.

Do not use this equipment for anything other than its intended use.

The use of accessory equipment not recommended by the manufacturer will void product listing and warranty and may cause an unsafe condition.

Any service on this equipment should be performed

 

by

 

qualified personnel only.

Equipment should be mounted in locations and at heights where it will not be subject to tampering by unauthorized personnel.

Do not ceiling mount.

Use caution when servicing batteries.

Cap unused wires with enclosed wire nuts or other approved method.

Make sure wire terminations are secure and leads are properly tucked in appropriate wire channels.

Summary of Contents for EU2C

Page 1: ...r BLACK ink PAGINATION 8 5 X 11 portrait CONFIGURATIONS PART INSTRUCT SHEET DESCRIPTION REV DATE STANDARD UNIT EU2C B 09 12 2018 X EMCSA00795 ABL LED WARNING X DATE CHANGE DESCRIPTION BY One Lithonia Way Conyers GA 30012 Phone 800 334 8694 www lithonia com PAGE 0 of 4 RRB HO X X 9 12 18 REV B Removed SD HO wiring diagram ABL not offering SD and hO together at this time REQUIRED INSTRUCTION SHEETS ...

Page 2: ... charge for at least 24 hours then normal operation of this unit should take effect To check press the TEST button The lamps on the unit should turn on IMPORTANT SAFEGUARDS When using electrical equipment basic safety precautions should always be followed including the following PAGE 1 of 4 Fig A J Box Fig B Fig C BATTERY CONNECTOR PLUG IN NOTE Complies with California Title 20 Product label is ma...

Page 3: ...nd push housing directly onto the back plate Apply continuous AC power 5 After battery has been left to charge for 24 hours test the unit by pushing the test switch and the LED lamp head will turn ON OPERATION 1 During an electrical power failure the LED lamps will automatically come on for a minimum of 90 minutes 2 To test press the TEST switch The emergency LED lamps will illuminate and LED indi...

Page 4: ...ly charged Allow battery to recharge for 24 hours and then retest If lights are still dim replace battery TROUBLESHOOTING Condition The emergency lights do not operate 1 If the charge indicator light is OFF Check that the circuit breaker for AC supply is ON 2 If the charge indicator light is ON Check that battery is properly connected If problem persists Replace battery If remote lamps where appli...

Page 5: ...stallation PAGE 4 of 4 One Lithonia Way Conyers GA 30012 Phone 800 334 8694 www lithonia com Part No EMCSA00911 REV B 2018 09 12 AC INPUT CONNECTOR MOUNTING PLATE LAMP READY TEST BATTERY RED BLACK WHITE YELLOW BLUE WHITE YELLOW BLUE LAMP RED BLACK WHITE 277V 120V 0V CHARGER BOARD ...