Lithonia Lighting ELM2 LED Installation Instructions Download Page 4

INSTALLATION INSTRUCTIONS

PAGE: 4 of 4

WIRING DIAGRAMS

Part #EMCSA00764 Rev. G

2016.09.14

NOTE for HO models:

Use of 10-12 AWG stranded wire required to connect remote lamp heads to maintain operating voltage when remote fi xtures are connected to the emergency lighting equipment. 

IMPORTANT CODE COMPLIANCE INFORMATION

In accordance with NFPA 101, documented testing of your emergency lighting system must be tested monthly for a minimum of 30 seconds and annually for 90 minutes. Refer to 
your local codes for any additional requirements that may apply.

NOTE:

 Unused input 

lead must be properly 
insulated with wire 
nut or other approved 
method

One Lithonia Way, Conyers GA 30012

Phone: 800-334-8694

www.lithonia.com

OPTIONAL VOLTAGE

ORANGE: 220V-240V

BLACK: 120V

WHITE: Neutral

OPTIONAL VOLTAGE

ORANGE: 220V-240V

BLACK: 120V

WHITE: Neutral

OPTIONAL VOLTAGE

ORANGE: 220V-240V

BLACK: 120V

WHITE: Neutral

OPTIONAL VOLTAGE

ORANGE: 220V-240V

BLACK: 120V

WHITE: Neutral

Summary of Contents for ELM2 LED

Page 1: ...TANCES MAY DAMAGE FIXTURE WHICH MAY RESULT IN PERSONAL INJURY WARNING RISK OF PERSONAL INJURY This product may have sharp edges Wear gloves to prevent cuts or abrasions when removing from carton handling installing and maintaining this product WHERE APPLICABLE Before wiring to power supply turn off electricity at fuse or circuit breaker Disconnect AC power and unplug battery before servicing Consu...

Page 2: ...ensure proper engagement of the snaps in the mounting plate to the housing DO NOT OVERTIGHTEN SCREWS With AC power turned off connect battery connector leads CAUTION Continuous AC power must be available at time of installation as damage to the battery will occur if the battery is connected to the charger board for more than 3 days Align the holes on the bottom of the housing with the circular sna...

Page 3: ...ct the connector Charger Board Replacement Flex the snap at each end of charger board and pull it straight out of the housing Disconnect lamphead wires from board and reconnect them to new board Slide charger board into place make sure it is se cured by the snaps on both ends Lens Removal Using small straight blade tool gently remove the lens from the lamp head as shown above Battery Replacement D...

Page 4: ...mergency lighting system must be tested monthly for a minimum of 30 seconds and annually for 90 minutes Refer to your local codes for any additional requirements that may apply NOTE Unused input lead must be properly insulated with wire nut or other approved method One Lithonia Way Conyers GA 30012 Phone 800 334 8694 www lithonia com OPTIONAL VOLTAGE ORANGE 220V 240V BLACK 120V WHITE Neutral OPTIO...

Reviews: