![Lister Petter alpha Series Operator'S Handbook Manual Download Page 13](http://html.mh-extra.com/html/lister-petter/alpha-series/alpha-series_operators-handbook-manual_1927882013.webp)
13
alpha series lWa/lWX genset operators' handbook
Manual
This mode allows manual control of the generator functions. Once in
Manual
mode
the module will respond to the start button, start the engine, and run off
load. If the engine is running off-load in the
Manual mode
and a
remote start
signal
becomes present, the module will automatically instruct the changeover
device to place the generator on load ('
Close generator
' becomes active (if
used)). Upon removal of the
remote start signal
, the generator remains on
load until either selection of the '
stop/reset
' or '
auto
' modes.
auto
This button places the module into its '
automatic
' mode. This mode allows
the module to control the function of the generator automatically. The module will
monitor the remote start input and mains supply status and once a start request is
made, the set will be automatically started and placed on load.
Upon removal of the starting signal, the module will automatically transfer the
load from the generator and shut the set down observing the stop delay timer and
cooling timer as necessary. The module will then await the next start event.
2.4.1 test (dse7x20 only)
This button places the module into its '
test
' mode. This allows an on load test
of the generator. Once in
test mode
the module will respond to the start
button, start the engine, and run on load.
2.4.2 start
This button is only active in STOP/RESET
or MANUAL
mode. Pressing
this button in manual or test mode will start the engine and run off load (manual)
or on load (test).
Pressing this button in STOP/RESET mode will turn on the CAN engine ECU
(when correctly configured and fitted to a compatible engine ECU)
Mute / lamp test
This button silences the audible alarm if it is sounding and illuminates all of the
LEDs as a lamp test feature.
transfer to generator
Allows the operator to transfer the load to the generator (when in Manual mode only)
open generator (dse7x20 only)
Allows the operator to open the generator (when in Manual mode only)
transfer to mains (dse7x20 only)
Allows the operator to transfer the load to the mains (when in Manual mode only)
Menu navigation
Used for navigating the instrumentation, event log and configuration screens.
For further details, please see the more detailed description of these items
elsewhere in this manual.
Summary of Contents for alpha Series
Page 1: ...P027 10623 lWA LWX Generating Set Operators Handbook ORIGINAL INSTRUCTIONS alpha series ...
Page 34: ...34 ...