Instructions for use
SCU 835 / SEC 15
6.13
eXtendedLineModule XLM 35
The sensor control unit
SCU 835
can communicate with the Securi-
X
-Line
of the IP-Integral fire alarm control panels as well as the SecuriFire series.
In this case an optional adapter plate for the
XLM 35
must
be installed in
the housing bottom of the device and connected with the connector at
P504
of the mainboard
MB SCI 835
. The following information can be
transmitted to the
FACP
via the Securi-
X
-Line (ring line):
Alarm status per cable port
I
/
II
for maximum
eight
alarm zones.
Fault status per cable port
I
/
II
for maximum
eight
fault zones.
Pre signal status per cable port
I
/
II
for maximum
eight
pre signal
zones.
Reset.
Important note
A maximum of
eight
zonal alarms, pre-signals or faults can be transmitted. If the
SCU 835
is pro-
grammed with more than
eight
zones, all defined zones
≥ 8
will be transmitted with the respective status
of zone
8
.
Mounting the adapter plate for
XLM 35
:
The sensor control unit
SCU 835
has to be opened for mounting the adapter plate.
Insert the provided combi-screws
M3x8
on the back of the adapter plate through the marked holes and fix
the spacers
M3x10
clockwise on the front as shown.
e
X
tended
L
ine
M
odule
XLM 35
as shown in the illustration, push onto the spacers and click on into place.
Page 66/112
LISTEC GmbH
60T328-02-LI-en / 29.01.2021
Fig. 139:
XLM 35
interface
Fig. 140:
XLM 35
interface
Fig. 141: Insert the combi-screws
M3x8
Fig. 142: Fix the spacers
M3x10
Fig. 144:
XLM 35
locked
Fig. 143: Click on
XLM 35
PZ1
6