background image

Troubleshooting Step By Step Procedure

The following is a step by step procedure to help in troubleshooting any problems with this
boiler.   These   steps   should   be   performed   only   by   qualified   personnel   with   experience   in
hydronic   heating   systems,   and   electrical   heating   equipment.   You   are   working   with   high
voltages and should be extremely careful.

Before energizing boiler, ensure system is full of water.

(1) Make   sure   that   there   is   power   to   the   boiler.   There   must   be   power   to   the   boiler   to

complete these troubleshooting steps.
 a) There   should   be   power   at   the   main   terminal   block.   You   should   read   120   volts

between L1 and N, 120 volts between L2 and N, and 240 volts between L1 and L2.

 b) Disconnect the thermostat wires from terminals T1 and T2. Measure the voltage at

the  top  of  the  boiler  at  each  heating  element.  If  you  read  voltage  at  any   of  the
elements,   then   the  element   relays  for  that  element  are  stuck  on  and   need   to  be
replaced.

 c) Next measure the voltage from the N terminal of the main terminal block to each

terminal of each heating element. If you read voltage at any of the elements, then a
single element relay for that element is stuck on and needs to be replaced.

(2) Check the fuse.

 a) Remove the fuse located inside the boiler. Check it for continuity. Replace with a

new fuse of the correct type if necessary.

 b) Otherwise replace the existing fuse.

(3) Check that there is 24 volt AC power on the secondary side of the transformer. There

must be 24 volt AC power on the secondary side of the transformer for the boiler to
operate. If there is no power the transformer needs to be replaced. When there is 24 volt
power to the board the “Power On” light on the board should be on.

(4) With the thermostat wires still disconnected, connect a jumper wire from terminal T1 to

terminal T2. The “Thermostat On” light should now be on.
 a) This should energize the pump relay to the right of the control board, you should

hear a click. If not check that there is 24 volt DC power on the two relay terminals
with purple wires.

 b) If there is no power at the relay, the control board needs to be replaced.
 c) If there is power, but the relay is not turning on, replace the relay.

(5) When the relay is energized, it will supply 120 volt power for running the pump.

 a) There should now be 120 volt AC power to the terminals labeled PL and PN.
 b) If there is no power, replace the relay.

17

Summary of Contents for LEB dc Series

Page 1: ...opriate antifreeze Do not use any other liquids especially methanol automotive antifreeze or any kind of oil Do not exceed 50 antifreeze TM LION BOILERS LEB dc dc dc dc Series Boiler Installation Manu...

Page 2: ...2...

Page 3: ...d for adequacy for the additional load of the boiler All models require connection of 240 volt single phase power to terminals L1 and L2 and connection of a neutral conductor to the N terminal see Fig...

Page 4: ...ng temperatures are generally 90 F to 110 F Minimum Recommended Operating Pressure 12 PSI Warning The control transformer is sized to power only the internal controls External devices must be powered...

Page 5: ...d valves are usually required to balance the flow in each circuit to provide uniform heating A zoned heating system is also possible with separate heating zones and individual thermostats in each zone...

Page 6: ...6 inches above the floor level 6 Install inlet and outlet piping 7 An expansion tank must be installed see Fig 3 to allow for water expansion as the system is heated Dissimilar Metals Do not connect d...

Page 7: ...a long cycle which allows the room temperature to rise too high before the boiler shuts down Adjustments should be made to the setting if required but should not exceed 0 1 amps per adjustment Newer e...

Page 8: ...ire system is full of water and thoroughly purged of air The automatic air vent is to assist in removing air from the top of the tank to prevent elements from burning out It alone is not sufficient in...

Page 9: ...cipator setting Check pump circulation Boiler operates continuously Check anticipator setting Boiler noisy Oversized pump Flow rate too high Flow rate too low Pump location incorrect Boiler not heatin...

Page 10: ...oiler The obligation of the Manufacturer to repair replace or refund the purchase price exists provided the defective part or complete unit is returned to the Manufacturer ANY AND ALL TRANSPORTATION C...

Page 11: ...ITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY THE MANUFACTURER S LIABILITY ON ANY CLAIM OF ANY KIND INCLUDING NEGLIGENCE WITH RESPECT TO THE GOODS OR SE...

Page 12: ...12...

Page 13: ...13...

Page 14: ...14...

Page 15: ...15...

Page 16: ...16...

Page 17: ...e elements then a single element relay for that element is stuck on and needs to be replaced 2 Check the fuse a Remove the fuse located inside the boiler Check it for continuity Replace with a new fus...

Page 18: ...h limit control c If the high limit light now comes on the hi limit control will need to be replaced d If the element relay indicator lights do not come on disconnect the temperature sensor by pulling...

Page 19: ...ve steps and the boiler is still not working please contact us for assistance Concept Manufacturing Inc Box 23008 RPO McGillivray Winnipeg Manitoba Canada R3T 5S3 Phone 204 284 9111 Fax 204 284 9229 E...

Reviews: