background image

(5) When the relay is energized, it will supply 120 volt power for running the pump,

and activate the control board.
 a) There should now be 120 volt AC power to the terminals labeled P2L and

P2N, as “STAT 2” has the jumper wire connected.

 b) If there is no power, replace the relay.
 c) Reconnect the jumper to the “STAT 1” terminals, there should now be 120

volt AC power to the terminals labeled P1L and P1N, as “STAT 1” has the
jumper wire connected.

(6) With the circuit board now activated, the power relays should turn on one at a

time. There is about a one to two minute delay before the first relay turns on,
and about the same for each additional relay. If they have not started to come on
as yet, temporarily turn up the temperature on the aquastat to the maximum
setting,   it   should   be   returned   to   the   normal   setting   when   you   are   finished
troubleshooting. The power relays for controlling the elements should now start
to turn on. It may take a minute or two for the first relay to turn on, and about
the same length of time for each subsequent relay to turn on. As each relay
turns on, one indicator light on the control board should come on as well.
 a) If   the   element   relay   indicator   lights   do   not   come   on,   disconnect   the

temperature sensor by pulling out the connector at the control board (the
one with the two gray wires).

 b) If the indicator lights now come on, after waiting for the one to two minute

delay between each element the temperature sensor needs to be replaced. If
the   indicator   lights   still   do   not   come   on   the   control   board   needs   to   be
replaced. 

 c) If the indicator lights come on, but the relays for the elements do not come

on then the low water cut off or the high limit control may be preventing
them from coming on. This may be due to a faulty component, or may be an
actual low water, or high temperature condition.

(7) If the boiler is equipped with the low water cut off option try the following only

when   you   are   sure   the   boiler   and   the   heating   system   are   completely   full   of
water.
 a) Unplug the low water cut off from the control board. Temporarily (no more

than one second) place a jumper wire across the two pins of the low water
cut   off   connector   on   the   control   board,   the   element   relays   should   all
immediately turn on.

 b) If the relays energize, replace the low water cut off, otherwise go on to the

next step.

(8) Temporarily  (no  more   than  one  second)  place   a  jumper  wire  across  the   two

terminals on the high limit control.
 a) If the relays energize, replace the high limit control.

(9) If all the relays energize and there is no heat, then check for power to each of

the heating elements.
 a) With   all   the   relays   energized,   check   that   there   is   power   to   each   of   the

elements with a volt meter. If there is no voltage reading, replace the relay

21

Summary of Contents for CEBR2 Series

Page 1: ...n appropriate antifreeze Do not use any other liquids especially methanol automotive antifreeze or any kind of oil Do not exceed 50 antifreeze LION BOILERS CEBR2 Series Boiler Installation Manual TM C...

Page 2: ...2...

Page 3: ...volt single phase power to terminals L1 and L2 and connection of a neutral conductor to the N terminal see Fig 4 Three phase models require connection of three phase power of the correct voltage to th...

Page 4: ...erature increases outdoors the heat output of the boiler will be decreased For example when it is 10 C outside the water temperature will be 32 C and when it is 5 C outside the water temperature will...

Page 5: ...40 32 CEBR2 208 11 11 25 208 3 31 2 40 32 CEBR2 208 15 14 7 208 3 40 8 60 48 CEBR2 208 22 22 5 208 3 62 5 100 80 CEBR2 208 30 29 4 208 3 81 6 125 100 CEBR2 600 15 14 7 600 3 14 1 20 16 CEBR2 600 30 2...

Page 6: ...g system Pressure will decrease at a rate of 0 433 psi per foot above the fill point An expansion tank must be included to allow for approximately 4 expansion of the water in the entire heating system...

Page 7: ...d as Zero Clearance may be mounted against combustible surfaces 4 Units must be mounted straight as shown in Fig 2 with the outlet at the top and the inlet on the bottom See Up Arrow on label on side...

Page 8: ...control board are closed and stop when these terminals are opened Thermostat 1 terminals STAT 1 controls pump 1 and thermostat 2 terminals STAT 2 control pump 2 the priority terminals Thermostat Conne...

Page 9: ...e being used Temperature Control Setting Aquastat The boiler has a temperature control knob known as an aquastat on the left hand side This sets the maximum temperature that the boiler will operate at...

Page 10: ...d thoroughly purged of air The automatic air vent is to assist in removing air from the top of the tank to prevent elements from burning out It alone is not sufficient in removing air from the entire...

Page 11: ...cipator setting Check pump circulation Boiler operates continuously Check anticipator setting Boiler noisy Oversized pump Flow rate too high Flow rate too low Pump location incorrect Boiler not heatin...

Page 12: ...inal purchase price to the current owner of the Boiler regardless of any prior attempt by the Manufacturer to repair or replace that Boiler The obligation of the Manufacturer to repair replace or refu...

Page 13: ...HETHER EXPRESS OR IMPLIED AND ALL SUCH OTHER WARRANTIES INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED AND EXCLUDED FROM T...

Page 14: ...14...

Page 15: ...15...

Page 16: ...16...

Page 17: ...17...

Page 18: ...18...

Page 19: ...19...

Page 20: ...voltage at any of the elements then the element relay for that element is stuck on and needs to be replaced 2 Check the fuse on models equipped with a fuse a Remove the fuse located inside the boiler...

Page 21: ...trol board the one with the two gray wires b If the indicator lights now come on after waiting for the one to two minute delay between each element the temperature sensor needs to be replaced If the i...

Page 22: ...ach element with an ohm meter and replace any elements as necessary If you have gone through the above steps and the boiler is still not working please contact us for assistance Concept Manufacturing...

Reviews: