background image

Troubleshooting Step By Step Procedure

The following is a step by step procedure to help in troubleshooting any problems with
this   boiler.   These   steps   should   be   preformed   only   by   qualified   personnel   with
experience   in   hydronic   heating   systems,   and   electrical   heating   equipment.   You   are
working with high voltages and should be extremely careful.

Before energizing boiler, ensure system is full of water.

(1) Make sure that there is power to the boiler. There must be power to the boiler

to complete these troubleshooting steps.
 a) On 240 volt single phase models there should be power at the main terminal

block. You should read 120 volts between L1 and N, 120 volts between L2
and N, and 240 volts between L1 and L2.

 b) On three phase models there should be power at the main terminal block.

You should take three readings on the main terminal block, you should read
the appropriate voltage for your model between L1 and L2, between L2 and
L3, and between L1 and L3. You should also read 120 volts on the terminal
block on the lower right side on the terminals labeled S

and S

N

.

 c) Disconnect the thermostat wires from the terminals “STAT 1” AND “STAT

2”. Measure the voltage at the top of the boiler at each heating element. If
you measure voltage at any of the elements, then the element relay for that
element is stuck on and needs to be replaced.

(2) Check the fuse on models equipped with a fuse.

 a) Remove the fuse located inside the boiler. Check it for continuity. Replace

with a new fuse of the correct type if necessary.

 b) Otherwise replace the existing fuse.

(3) Check that there is 24 volt AC power on the secondary side of the transformer.

These  are the  two  wires running  from the  transformer  to the  control board.
There must be 24 volt AC power on the secondary side of the transformer for
the boiler to operate. If there is no power the transformer needs to be replaced.

(4) With the thermostat wires still disconnected from step (1)c), disconnect the

outdoor sensor as well, then connect a jumper wire from one terminal of STAT 1
to the other terminal of STAT 1.
 a) This should energize the left hand Pump Relay to the right of the control

board, you should hear a click. If not check that there is 24 volt AC power on
the two terminals with purple wires going to this relay.

 b) Remove   the   jumper   wire   from   the   “STAT   1”   terminals,   and   jumper   the

“STAT 2” terminals. This should energize the right hand Pump Relay. If not
check that there is 24 volt AC power on the two terminals with purple wires
going to this relay.

 c) If there is no power at the relay, the control board needs to be replaced.
 d) If there is power, but one of the relays is not turning on, replace that relay.

20

Summary of Contents for CEBR2 Series

Page 1: ...n appropriate antifreeze Do not use any other liquids especially methanol automotive antifreeze or any kind of oil Do not exceed 50 antifreeze LION BOILERS CEBR2 Series Boiler Installation Manual TM C...

Page 2: ...2...

Page 3: ...volt single phase power to terminals L1 and L2 and connection of a neutral conductor to the N terminal see Fig 4 Three phase models require connection of three phase power of the correct voltage to th...

Page 4: ...erature increases outdoors the heat output of the boiler will be decreased For example when it is 10 C outside the water temperature will be 32 C and when it is 5 C outside the water temperature will...

Page 5: ...40 32 CEBR2 208 11 11 25 208 3 31 2 40 32 CEBR2 208 15 14 7 208 3 40 8 60 48 CEBR2 208 22 22 5 208 3 62 5 100 80 CEBR2 208 30 29 4 208 3 81 6 125 100 CEBR2 600 15 14 7 600 3 14 1 20 16 CEBR2 600 30 2...

Page 6: ...g system Pressure will decrease at a rate of 0 433 psi per foot above the fill point An expansion tank must be included to allow for approximately 4 expansion of the water in the entire heating system...

Page 7: ...d as Zero Clearance may be mounted against combustible surfaces 4 Units must be mounted straight as shown in Fig 2 with the outlet at the top and the inlet on the bottom See Up Arrow on label on side...

Page 8: ...control board are closed and stop when these terminals are opened Thermostat 1 terminals STAT 1 controls pump 1 and thermostat 2 terminals STAT 2 control pump 2 the priority terminals Thermostat Conne...

Page 9: ...e being used Temperature Control Setting Aquastat The boiler has a temperature control knob known as an aquastat on the left hand side This sets the maximum temperature that the boiler will operate at...

Page 10: ...d thoroughly purged of air The automatic air vent is to assist in removing air from the top of the tank to prevent elements from burning out It alone is not sufficient in removing air from the entire...

Page 11: ...cipator setting Check pump circulation Boiler operates continuously Check anticipator setting Boiler noisy Oversized pump Flow rate too high Flow rate too low Pump location incorrect Boiler not heatin...

Page 12: ...inal purchase price to the current owner of the Boiler regardless of any prior attempt by the Manufacturer to repair or replace that Boiler The obligation of the Manufacturer to repair replace or refu...

Page 13: ...HETHER EXPRESS OR IMPLIED AND ALL SUCH OTHER WARRANTIES INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED AND EXCLUDED FROM T...

Page 14: ...14...

Page 15: ...15...

Page 16: ...16...

Page 17: ...17...

Page 18: ...18...

Page 19: ...19...

Page 20: ...voltage at any of the elements then the element relay for that element is stuck on and needs to be replaced 2 Check the fuse on models equipped with a fuse a Remove the fuse located inside the boiler...

Page 21: ...trol board the one with the two gray wires b If the indicator lights now come on after waiting for the one to two minute delay between each element the temperature sensor needs to be replaced If the i...

Page 22: ...ach element with an ohm meter and replace any elements as necessary If you have gone through the above steps and the boiler is still not working please contact us for assistance Concept Manufacturing...

Reviews: