4 Description of the Connectors / Interfaces
4.1 PE
PE
Protective Earth
1
PE
PE, Protective Earth
- Use min 4 mm
2
(AWG 11)
- Tightening Torque 2 Nm (18 lbin)
4.2 X30
X30
Supply Mains
2, 3, 4
1
L1, L2, L3
PE
3x400-480 V
AC
50/60 Hz
PE, Protective Earth
- Tightening torque: 0.8 Nm (7 lbin)
- Use 60/75°C copper conductors only
- Conductor cross-section 2.5 - 4 mm
2
/ AWG 24 - 12
- Stripping length: 10 mm
- external circuit breaker (16 A Type C UL listed) required
- total conductor length must be 10 m or less
4.3 X56
X56
DC Output
4, 5
1, 2, 3
PWR+
PGND
Positive output
Negative output
- Tightening torque: 0.8 Nm (7 lbin)
- Use 60/75°C copper conductors only
- Conductor cross-section 2.5 - 4 mm
2
/ AWG 24 - 12
- Stripping length: 10 mm
- total conductor length must be 10 m or less
5 LED Blink Codes
LED Blink Codes
enabled
error
Description
On
Off
Power supply is enabled
Off / On
On
Error occurred
PE
2
3
PE
2
3
P
P
PGN
PGN
P
P
P
G
N
P
G
N
P
G
N
PGN
error
enabled
Summary of Contents for S02-72/1000
Page 11: ...Installation Guide Power Supply ENG NTI AG LinMot Type S02 72 1000 Page 11 17 ...
Page 12: ...Installation Guide Power Supply ENG Page 12 17 Type S02 72 1000 NTI AG LinMot ...
Page 13: ...Installation Guide Power Supply ENG NTI AG LinMot Type S02 72 1000 Page 13 17 ...
Page 14: ...Installation Guide Power Supply ENG Page 14 17 Type S02 72 1000 NTI AG LinMot ...
Page 15: ...Installation Guide Power Supply ENG NTI AG LinMot Type S02 72 1000 Page 15 17 ...