7.12.2 Parameters
The acknowledge input is not configurable and has no parameters.
7.13 Safe Digital Output
7.13.1 Description
The drive supports one safe digital output, which is located on the safe I/O connector X49.
The X49 connector has the following signal layout:
X49
Safe Digital IO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
X49A
SafeDigIn 1A- (safe digital input 1 channel A negative)
SafeDigIn 1B- (safe digital input 1 channel B negative)
SafeDigIn 2A- (safe digital input 2 channel A negative)
SafeDigIn 2B- (safe digital input 2 channel B negative)
DGND
DigInAck- (non-safe Acknowledge negative)
SafeDigOut A (safe digital output channel A)
X49B
SafeDigIn 1A+ (safe digital input 1 channel A positive)
SafeDigIn 1B+ (safe digital input 1 channel B positive)
SafeDigIn 2A+ (safe digital input 2 channel A positive)
SafeDigIn 2B+ (safe digital input 2 channel B positive)
GND
D (non-safe Acknowledge positive)
SafeDigOut B (safe digital output channel B)
- Use 60/75 °C copper conductors only
- Conductor cross-section max. 1.5 mm
2
- Stripping length: 10mm.
Table 60: X49 Connector: Safe Digital Output
The safe digital output is realized as a dual channel output, with test pulse.
The output is short circuit safe. The output is not galvanically isolated.
The output switches 24V, supplied on X4.
The output is monitored.
State
Current consumption
Value
Low
< 1 mA
< 5 V
High
High, max. 100 mA
> 15 V
Table 61: Output level definitions
2S Drive Systems / 0185-1174_E_1V1_SM_C1251-2S / NTI AG
0185-1174_E_1V1_SM_C1251-2S / 2021-11-26 16:43 (Rev. 12500)