PROGRAMMING OPTIONS

There are several AK-31 programming options. For most 
installations, the factory set default options are suffi cient. The 
keypad must be in Programming Mode to make these changes.

Select Door Sense or Inhibit Input 

Default: Door Sense

The input (gray wire) can be programmed for 

DOOR SENSE

 or 

INHIBIT

.

Press:

  

1 0 #

 

Input 

#

Input

 = 0 for Door 

S

ense, = 1 for Inhibit

When programmed for 

DOOR SENSE

, if an open condition on the input occurs 

before access is granted (with an entry code or with the request-to-enter input) a 

FORCED ENTRY

 output will occur. If an open condition remains 60 seconds after 

a relay activation for access, a 

DOOR AJAR

 output will occur.

When programmed for 

INHIBIT

, a closed condition on the input will prevent 

Relay #1 from activating when access is requested with an entry code. This mode 
is typically used with an external timer to disable the access device at certain 
times.

Select Forced Entry Output 

Default: Output #3

Sets which output activates if the 

DOOR SENSE

 input opens before access is 

granted. This output is not timed.

Press:

  

1 1 #

 

Output

 

#

Output

 = Output to Activate (0-4)

1 = Main Relay  2 = Auxiliary Relay  

3

 = Output #

3

  4 = Output #4  0 = No Output

Select Door Ajar Output 

Default: Output #4

Sets which output activates if the 

DOOR SENSE

 input stays open 60 seconds 

after access is granted. This output is not timed.

Press:

  

1 2 #

 

Output

 

#

Output

 = Output to Activate (0-4)

1 = Main Relay,  2 = Auxiliary Relay,  

3

 = Output #

3

,  4 = Output #4,  0 = No Output

Select Keypad Lockout Output 

Default: No Output

Sets which output activates when the keypad is “locked out” after too many 
incorrect entry code attempts. The lockout time is 60 seconds.

Press:

  

3

 #

 

Output

 

#

Output

 = Output to Activate (0-4)

1 = Main Relay,  2 = Auxiliary Relay,  

3

 = Output #

3

,  4 = Output #4,  0 = No Output

Select Keypad Active Output 

Default: No Output

Sets which output activates when any keys are pressed. This output is timed. If 
toggle mode is selected for the output, the timer value defaults to 2 seconds.

Press:

  

1 4 #

 

Output

 

#

Output

 = Output to Activate (0-4)

1 = Main Relay,  2 = Auxiliary Relay,  

3

 = Output #

3

,  4 = Output #4,  0 = No Output

Select Alarm Shunt Output 

Default: No Output

Sets which output activates during the time access is granted. (Use this output 
to shunt alarm contacts attached to the access door.) This output may be timed 
or toggled.

Press:

  

1 5 #

 

Output

 

#

Output

 = Output to Activate (0-4)

1 = Main Relay,  2 = Auxiliary Relay,  

3

 = Output #

3

,  4 = Output #4,  0 = No Output

Select Request-to-Exit Output 

Default: Main Relay

Sets which output activates when the Request-to-Exit input is grounded. This 
output may be timed or toggled.

Press:

  

1 6 #

 

Output

 

#

Output

 = Output to Activate (0-4)

1 = Main Relay,  2 = Auxiliary Relay,  

3

 = Output #

3

,  4 = Output #4,  0 = No Output

Main Relay On-time 

Default: 2 Seconds

Sets the length of time the Main Relay activates when triggered.

Press:

  

2 1 #

 

Seconds

 

#

Seconds

 = Output time in seconds (0-60)

Auxiliary Relay On-time 

Default: 2 Seconds

Sets the length of time Auxiliary Relay activates when triggered.

Press:

  

2 2 #

 

Seconds

 

#

Seconds

 = Output time in seconds (0-60)

Solid-state Output #3 On-time 

Default: 2 Seconds

Sets the length of time Output #3 activates when triggered.

Press:

  

3

 #

 

Seconds

 

#

Seconds

 = Output time in seconds (0-60), 99 = Toggle Mode

Solid-state Output #4 On-time 

Default: 2 Seconds

Sets the length of time Output #4 activates when triggered.

Press:

  

2 4 #

 

Seconds

 

#

Seconds

 = Output time in seconds (0-60), 99 = Toggle Mode

Beep Sounds on Keystrokes 

Default: Yes

Selects whether or not the keypad beeps as each key is pressed.

Press:

  

4 0 #

 

Sound

 

#

Sound

 = 1 for Yes, = 0 for No

Beep Sounds During Main Relay 

Default: No

Selects whether or not the keypad beeps during Main Relay activation.

Press:

  

4 1 #

 

Sound

 

#

Sound

 = 1 for Yes, = 0 for No

Beep Sounds During Auxiliary Relay 

Default: No

Selects whether or not the keypad beeps during Auxiliary Relay activation.

Press:

  

4 2 #

 

Sound

 

#

Sound

 = 1 for Yes, = 0 for No

Beep Sounds During Output #3 

Default: No

Selects whether or not the keypad beeps during Output #3 activation.

Press:

  

3

 #

 

Sound

 

#

Sound

 = 1 for Yes, = 0 for No

Beep Sounds During Output #4 

Default: No

Selects whether or not the keypad beeps during Output #4 activation.

Press:

  

4 4 #

 

Sound

 

#

Sound

 = 1 for Yes, = 0 for No

228037 A    IMAGE 7

Summary of Contents for AK-31

Page 1: ...1 2 3 4 5 6 7 8 9 0 AK 31 Digital Keyless Entry System 760 438 7000 USA Canada 800 421 1587 800 392 0123 Toll Free FAX 800 468 1340 www linearcorp com Installation and Programming Instructions ...

Page 2: ...s and programming even without power An internal jumper is provided to reset the master code The Main Relay has a 5 Amp capacity The Auxiliary Relay has a 1 Amp capacity Two solid state outputs capable of switching 100 mA to common are programmable to signal forced entry door ajar lockout alarm circuit shunting request to exit and keypad active conditions FEATURES KEYPAD PROGRAMMABLE No programmer...

Page 3: ...DC MAX AUXILIARY RELAY 1 AMP 28 VDC MAX TERMINAL BLOCK 1 WIRES AK 31 TERMINALS CAUTION IF THE UNIT IS AC POWERED MAKE SURE THE SECONDARY OF THE SYSTEM TRANSFORMER IS ISOLATED FROM EARTH GROUND OPTIONAL WIRING REQUIRED WIRING OTHER WIRING NOTES 1 ALARM SHUNT SET FOR AUXILIARY RELAY 2 GRAY WIRE SET FOR DOOR SENSE GROUND STAKE N C DOOR SWITCH ALARM CONTACT TO ALARM SYSTEM POWER SUPPLY ELECTRIC DOOR S...

Page 4: ...in the wall Screw the mounting plate onto the electrical box see Figure 4 Final Keypad Installation After wiring the keypad see next page complete the installation by securing the keypad to the mounting plate If a lower beeper sound level is required before installing the keypad remove Jumper at P4 place the jumper block on one pin to save the jumper Hook the keypad assembly onto the mounting plat...

Page 5: ...e switch to the keypad box Connect the door switch to the keypad s SENSE input gray wire E8 and COM any black wire If an inhibit switch or timer is going to be used for temporarily disabling the keypad route two wires from the switch or timer to the keypad box Connect the inhibit switch timer normally open terminals to the keypad s SENSE input gray wire E8 and COM any black wire REQUEST TO EXIT IN...

Page 6: ... during programming to clear the keypad and re enter the command Press 9 Setting Entry Code Length Default 4 digits Press 0 3 Length Length 1 6 for entry code length NOTE If the Entry Code Length is going to be changed from the factory default of four digits make this change first before programming any entry codes Adding a New Entry Code Press 01 Code Code Action Code The new entry code 1 999999 ...

Page 7: ...o 2 seconds Press 1 4 Output Output Output to Activate 0 4 1 Main Relay 2 Auxiliary Relay 3 Output 3 4 Output 4 0 No Output Select Alarm Shunt Output Default No Output Sets which output activates during the time access is granted Use this output to shunt alarm contacts attached to the access door This output may be timed or toggled Press 1 5 Output Output Output to Activate 0 4 1 Main Relay 2 Auxi...

Page 8: ...maximum ENVIRONMENTAL Temperature 22 F to 149 F 30 C to 65 C Humidity 5 to 95 non condensing LINEAR LIMITED WARRANTY This Linear product is warranted against defects in material and workmanship for twenty four 24 months The Warranty Expiration Date is labeled on the product This warranty extends only to wholesale customers who buy direct from Linear or through Linear s normal distribution channels...

Reviews: