10
Shows the confi gured parameter and the maximum permitted leakage fl ow
rate.
•
Press the
à
to start the test.
•
A self test is carried out before the test starts.
•
The test starts once the selected pressure is reached, and continues for
fi ve minutes.
•
You can interrupt the test at any time by pressing Stop.
While the test is running, the achieved pressure and the current fl ow rate
are displayed.
•
After the test duration of 300 s, the device stops automatically. (Stand-
ardised test duration) If you press Stop to end the test early, the results
are displayed.
•
The device indicates whether the test has passed or failed with the
specifi ed parameters.
•
Press the Print key to print the report or press the New key to start a
new test.
Viewing the report before printing.
•
You can use the
á
or
â
key to scroll through the report.
•
Switch on the TD 600 printer and place it close to the IR window.
•
Press OK to start printing.
•
Note: The report is not permanently stored unless you select "Save" on
the menu.
Chart:
•
Press the MENU key and press the
á
or
â
key to select Chart from the
menu.
•
Confi rm by pressing the
à
key.
•
You can print the chart by pressing the Print key on the TD 600.
•
To return to the menu press the Menu or New key once.
•
To start a new test, press the Menu key twice.
About the chart:
The bar chart shows the permitted leakage fl ow rate for the airtightness classes, with the specifi ed m2 and the actual
test pressure. The test value appears as a red line.
Compliant airtightness classes are shown with green bars. Non-compliant classes are shown with red bars.