3.0 Maintenance

The interval of cleaning depends on the indoor environment where the panel is placed. 
Under optimal conditions the Atrium Plana panels only need cleaning every 5 years. 

3.1  Cleaning instructions 

 

– Only use lukewarm water and a mild detergent.

4.0  Product and system specification

4.1  Material data

Atrium Plana  40

Atrium Plana  60

Dry weight, kg/m

2.1

3.0

Water content, l/m

0.40

0.8

Copper pipes, quality

EN12735-2 CU-DHP

EN12735-2 CU-DHP

Pressure class

PN10

PN10

4.2  Environmental declaration

 

– Please visit 

www.lindqst.com

•  Select Documentation Finder
•  Select “Atrium Plana ”
•  Select “Environmental declaration”

4.3  Working and test pressure 

 

– Lindab’s waterborne products have been manufactured and tested according to 

the Pressure Equipment Directive 97/237EC. The products are classified as SEP – 
Sound Engineering Practice.

 

– Pressure table
 

Pressure class

PN10

Max. working pressure

10 bar

Max. recommended dynamic pressure

0.2 bar

Max. test pressure

16 bar

 

– Even though the battery of the chilled panel can withstand a very high static 

working pressure, we recommend a much lower dynamic working pressure, to 
avoid noise issues from the valves.

Summary of Contents for Atrium Plana 40

Page 1: ...lindab we simplify construction Atrium Plana Service maintenance...

Page 2: ...ustain dents scratches or bends during installation Always seek to lift the panel at multiple points Do not lift in pipes Do not lift in edges Each panel is equipped with protective film to avoid any...

Page 3: ...e is covered by a plastic or rubber protection cover which should be removed before installation After removing the protection cover make sure that the pipe is intact and undamaged especially at the p...

Page 4: ...ipe work While mounting a compression fitting the pipe will be exposed to a big amount of force creating a risk of crushing the pipe To ensure that the pipe won t be crushed when mounting the compress...

Page 5: ...e connection pipes are internally soft welded why it s not allowed to solder the panel to the pipes 1 4 3 Flex hoses Our flexible hoses can be used with both compression and Tectite fitting We recom m...

Page 6: ...ide and the outside using a deburring tool before installation Mount a push on fitting to the pipe Make sure to press the fitting all the way onto the pipe After mounting the push on fitting mount the...

Page 7: ...ion above water connection Label location interior Under insulation above water connection On the label you ll find Order Order identification number Pos Order position Product Product configuration P...

Page 8: ...ty EN12735 2 CU DHP EN12735 2 CU DHP Pressure class PN10 PN10 4 2 Environmental declaration Please visit www lindqst com Select Documentation Finder Select Atrium Plana Select Environmental declaratio...

Page 9: ...ld up air in the system The water should be oxygen free to prevent corrosion The water system must be filled with potable water that complies with the EC directive 98 83 EC pH value of water must be b...

Page 10: ...usohjeet sek tuotetuen yhteystiedot www lindab fi Oikeus muutoksiin pid tet n DE Hier finden Sie aktuelle Produktinformationen Mon tageanleitungen und Telefonnummer E Mail Adressen der Ansprechpartner...

Reviews: