Lincoln Electric Wire Feed Module 12207 Operator'S Manual Download Page 16

A-8

INSTALLATION

WIRE FEED MODULE™

CONNECTION OF LINCOLN ELECTRIC WIRE FEEDERS

Shut off welder before making any electrical  connections.
------------------------------------------------------------------

CONNECTION OF LN-25 TO THE WIRE FEED MODULE

The LN-25 with internal “COLD TIP” contactor requires the K2614-6
Control Cable for voltage control at the feeder.

The LN-25 with internal “Cold Tip” Contactor can be operated without
a control cable (Volt sensing mode) if voltage control at the wire feed-
er is not desired.

See the appropriated connection diagrams in the Diagrams section.

a)  Shut off the welder.

b)  Connect the electrode cable from the LN-25 to the positive stud of

the welder.  Connect the work cable to the CV negative stud of the
welder.  (NOTE:  reverse the connections for negative electrode
polarity.)

c)  For LN-25’s with internal contactor, connect the K2614-6 remote

voltage control cable from the LN-25 to the14-pin receptacle on
the control panel.

d)  Attach the single lead from the front of the LN-25 to the work

using the spring clip on the end of the lead.  This is a control lead
to supply current to the wire feeder motor; it does not carry weld-
ing current.  Set the polarity switch on the LN-25 to the proper
polarity.

e)  Set the “Current Range Selector” switch to the “190-120” position

for most common processes, this may be changed if a different
arc characteristic is preferred.

f)  Set the “LOCAL/REMOTE” Control switch to the “REMOTE” posi-

tion. If operating an LN-25 with internal “Cold Tip” Contactor but
without the K2614-6 Remote Voltage Control Cable set the
“Local/Remote” Control Switch to the “Local” position.

g)  Set the “IDLER” switch to the “HIGH” position.  The “AUTO” posi-

tion may be used with some high current processes.

CONNECTION OF THE LN-7, LN-7 GMA TO THE WIRE FEED
MODULE

Requires K584-(L) input cable, K864 adapter and optionally the
K857 for remote control.  See the connection diagram in the
Diagrams section.

a)  Shut the welder off.

b)  Connect the electrode cable from the LN-7 to the positive stud

of the welder.  Connect the work cable to the CV negative stud
of the welder.  (

NOTE

:  Reverse the connections for negative

electrode polarity.)

c)  Connect the LN-7 per the instructions on the appropriate con-

nection diagram.

d)  Set the “Current Range” switch to the “190-120” position for

most common processes, this may be changed if a different
arc characteristic is desired.

e)  Set the “LOCAL/REMOTE” control toggle switch to “REMOTE”.

f)  Set the “IDLER” switch to the “AUTO” position.  The “HIGH”

position may be required when used with some low current
processes.

CONNECTION OF THE LN-23P TO THE WIRE FEED MODULE

Requires the K350-1 adapter kit.  Adapter kit provides an isolated
trigger voltage and allows connection of two wire feeders.  See
connection diagram in the Diagrams section.

a)  Shut the welder off.

b)  Connect the electrode cable from the LN-23P to the CV nega-

tive output stud of the engine welder.  Connect the work cable
to the positive output stud.

c)  Mount K350-1 adapter per instructions included with adapter.

d)  Connect LN-23P per instructions on appropriate connection

diagram.

e)  Connect control lead marked “21” to work connection.  Refer

to connection diagram in Diagrams section for routing instruc-
tions and wire size.

f)  Set the “Current Range Selector” switch to the “190-120”

(middle position) for most common processes, this may be
changed if a different arc characteristic is preferred.

g)  Set the “LOCAL/REMOTE” control toggle switch to “REMOTE”.

h)  Set the idler switch to the “AUTO” position.  The “HIGH” posi-

tion may be required when welding with low current process-
es.

WARNING

Summary of Contents for Wire Feed Module 12207

Page 1: ...achines having Code Numbers 12207 Need Help Call 1 888 935 3877 to talk to a Service Representative Hours of Operation 8 00 AM to 6 00 PM ET Mon thru Fri After hours Use Ask the Experts at lincolnelec...

Page 2: ...A LARGE ROOM OR OUTDOORS natural ventilation may be adequate if you keep your head out of the fumes See below USE NATURAL DRAFTS or fans to keep the fumes away from your face If you develop unusual s...

Page 3: ...hot engine parts and igniting Do not spill fuel when filling tank If fuel is spilled wipe it up and do not start engine until fumes have been eliminated 1 d Keep all equipment safety guards covers and...

Page 4: ...m to ANSI Z87 I standards 4 b Use suitable clothing made from durable flame resistant material to protect your skin and that of your helpers from the arc rays 4 c Protect other nearby personnel with s...

Page 5: ...nt passing through lifting chains crane cables or other alternate circuits This can create fire hazards or overheat lifting chains or cables until they fail 6 h Also see item 1 c 6 I Read and follow N...

Page 6: ...ri s et non inflammables 4 Des gouttes de laitier en fusion sont mises de l arc de soudage Se prot ger avec des v tements de protection libres de l huile tels que les gants en cuir chemise paisse pan...

Page 7: ...nection of Lincoln Electric Wire Feeders A 8 OPERATION Section B Design Features B 1 Recommended Wire Feeders and Accessories B 1 Additional Safety Precautions B 1 Wire Feed Module Operation B 1 MAINT...

Page 8: ...ectrode welding and other open arc processes With the module installed the welder can be easily set to operate in either the constant voltage or the stan dard constant current modes The constant volta...

Page 9: ...top engine before servicing Keep away from moving parts Only qualified personnel should install use or service this equipment MACHINE GROUNDING Because a portable engine driven welder or generator cre...

Page 10: ...all Flat Head Screwdriver Pliers 3 32 Allen Wrench 3 8 Drive Ratchet with Small Extension 1 2 Socket 9 16 Deep Well Socket 3 4 Socket 5 16 Nut Driver and Socket 1 2 Open End Wrench 9 16 Open End Wrenc...

Page 11: ...all wires connected to it mounting tab down INSTALLATION SEQUENCE SAE 300 HE See Exploded View the following Page 1 Remove the bottom 3 mounting screws from the upper control nameplate Keep the screw...

Page 12: ...ENTIOMETER SPACER AMPHENOL RECEPTACLE MOUNT WITH KEY LOCATED IN THE BOTTOM POSITION POTENTIOMETER SHAFT SEAL CONTROL KNOB CENTER SHAFT SEAL AND SPACER UNDER KNOB AND WITH PRESSURE ON THE KNOB AGAINST...

Page 13: ...eed power cable assembly through the rectangu lar window on the bottom of the generator 8 Connect power cable thermostat assembly and the existing cables to the negative brushholder using the 75 long...

Page 14: ...right side of the machine and save hardware 12 Position control box into place Four plastic fuel tank mounting bolts require loosening to slide the tank towards the engine The control box must be mane...

Page 15: ...e guard from the left side of the welder Using two screws from the mounting hardware package fasten the out put terminal also from the mounting hardware package to the guard Connect the WFM control bo...

Page 16: ...t processes CONNECTION OF THE LN 7 LN 7 GMA TO THE WIRE FEED MODULE Requires K584 L input cable K864 adapter and optionally the K857 for remote control See the connection diagram in the Diagrams secti...

Page 17: ...standard output terminal is not used for CV welding of either polarity Refer to diagrams section to determine the correct con nection to the remote control receptacle When the WFM is in the CV mode th...

Page 18: ...tle linkage will cause an increase in the A C auxiliary voltage If this voltage goes above 140 volts the control circuits of the WFM and wire feeders will be damaged The engine governor setting is pre...

Page 19: ...do not understand or are unable to perform the Recommended Course of Action safely contact your local Authorized Field Service Facility TROUBLESHOOTING CHART Have qualified personnel do the maintenanc...

Page 20: ...ion 2 Refer to quick check procedure for generator only 3 Refer to procedure for Checking the Cold Tip Contactor CR4 4 Turn engine off Remove short circuit 5 Broken or loose connections from WFM to co...

Page 21: ...Capacitors in power source output cir cuit failed A failure is indicated if the small vent plug on the top of a capaci tor is raised or blown out 5 Opening in feedback circuit 6 Faulty P C Board 1 Ch...

Page 22: ...ion contamination or looseness b Check leads in the plug harness for loose or inter mittent connection 2 If P C Board is visibly damaged electrically before possibly subjecting the new P C Board to th...

Page 23: ...voltage is present at leads 630 631 measure the voltage between L2 terminal and ter minal opposite L2 If the voltage is equal to the output voltage across the positive and negative output terminals r...

Page 24: ...the problem exists in the Wire Feed Module Refer to Troubleshooting chart 2 If there is no generator output in step 1 proceed with the following a If jumper plug P10 is available a quick check can be...

Page 25: ...may not be accurate for all machines covered by this manual The specific diagram for a particular code is pasted inside the machine on one of the enclosure pan els If the diagram is illegible write to...

Page 26: ...GATIVE CV OUTPUT TERMINAL PANEL CONNECT TO NEG BRUSH HOLDER 250 AMP THERMOSTAT ASSEMBLY WIRE FEED MODULE ON MACHINE REMOVE PLUG P10 FROM CONNECTOR J5 CONNECT P5 ON W F M TO CONNECTOR J5 ON MACHINE CON...

Page 27: ...parts or electrode with skin or wet clothing l Insulate yourself from work and ground l No toque las partes o los electrodos bajo carga con la piel o ropa moja da l Aislese del trabajo y de la tierra...

Page 28: ...d Entl ftung des Arbeitsplatzes l Mantenha seu rosto da fuma a l Use ventila o e exhaust o para remover fumo da zona respirat ria l Turn power off before servicing l Desconectar el cable de ali mentac...

Page 29: ...tomer s particular purpose with respect to such information or advice As a matter of practical consideration we also cannot assume any responsibility for updating or correcting any such information or...

Reviews: