B-2
OPERATION
CONTROL
The Eaton 2DD Smartwire I/O pack produces both an input and an
output when connected to a robotic welding cell. When the unit is
powered on and operating, the remote output will produce a
24VDC "running" signal. If dry contact is made between the input
and 24V source line the Fan Running Light will illuminate green.
Starting remotely prevents the local panel button from stopping
the unit, as a maintained start signal will take precedence. For
further details consult the "Smartwire Connections Diagram" in
section "F" of this manual.
NOTE: when the unit's Alarm Light is illuminated the remote
output will change to a pulsing high/low at a rate of approx-
imately 1hz. For remote activation, the Robotic Welding Cell
start/stop simulator feature may be utilized (see section "F" of this
manual).
FIGURE B.1
A. Power On (Light)
B. Alarm (Light)
C. Fan Running (Light)
D. Reset Drive Alarm (Switch)
E. Start/Stop fan (Switch)
F. Main Switch - Input Power
Display System Control Panel
FIGURE B.2
Functions
A. POWER
Light (white): indicates the unit has power, is online,
and available for operation. Blinking light indicates that filter
cleaning is in progress.
B. ALARM
Light (red): indicates one of two potential issues with
the unit. Blinking light indicates the filter differential pressure
has surged above the maximum DP Alarm set point for two
hours continuously and the filter should be changed. Solid
light indicates that the fan's Variable Speed Starter (VSS) has
faulted.
C. FAN RUNNING
Light (green): indicates the unit is operational
and fan is running. Blinking light indicates that the fan
cannot be restarted until after a 30 second delay. This
protects the VSS from over current due to rapid off/on
cycles.
D. RESET DRIVE ALARM BUTTON
Resets the VFD fault. You may have to manually reset the
drive on it's front panel display-- Refer this activity to
qualified maintenance service personal who are allowed
inside a powered control cabinet.
E. START/STOP FAN
Button: starts the fan operation when the
unit is online, and also stops the fans if already operational.
NOTE - Fans will NOT stop if the unit has been remotely started.
NOTE - Reference control panel label for wiring specifications
NOTE - Land power ground wire should be longer than all other
wires
A
B
C
E
F
D
PRISM COMPACT
®
NOTE - A jumper wire removed can disable the front panel start
button and only allow the remote start to be active, refer
to the electrical diagram for this feature on what wire to
remove.