5. Control Function Description 

5.1 Compressor Control

 

● When the temperature 

“MAX TEMP”, and the time that the compressor has stopped 

“the valve of 

U10”, the compressor starts. 

● When the temperature 

“MIN TEMP”, and the time that the compressor has run 

“the valve of U11”, 

the compressor stops. 

● Compressor emergent on 

Press and hold “▼” key for five seconds, the compressor will power on if the following meets:

 

◆ 

controller in non-defrosting status 

◆ 

controller in non-dropping water status 

◆ 

the compressor stops 

In compressor emergent on status, press and hole “▼” key for five seconds, the mode exits. 

5.2 Compressor Delay Protection   

● After power supply, the compressor is able to start only after the time(U10) has passed. 

● After the compressor stops, it is able to restart again only after the time(U10) has passed. 

● After the compressor starts, it is able to stop only after the time(U11) has passed. 

5.3 Temperature Sensor Failure Protection: Protected Running Mode

 

● 

When the room temperature sensor fails, the system will  automatically run in the protected running 

mode. In this mode, the compressor will run and stop with the period of 30 minutes. Compressor works 

for U12* 3 minutes, stop for 

30 - (U12* 3) 

minutes. 

Note: If U12=0, system stops when sensor fails

 

5.4 High-temperature and Low-temperature warning

 

● 

When  the  test  temperature  ≥  “MAX  TEMP”+  “U50”,and  the  time  reaches  to  “U52  or  U53

”,high 

temperature  warning  starts. 

● 

When  the  test  temperatur

≦ 

“MIN  TEMP”+  “U51”,and  the  time 

reaches to “U52 or U53

”,low temperature warning starts. 

5.5 External input warning 

There are several ways for the external warning input to this device: 

  On: Close, warning starts. When ok, input opens. Off: Open, warning starts. When ok, input closes. 

  Lock: when the external warning input signal disappears, system keep warning, Only press the key, 

can warn stop.    Unlock: when the external warning input signal disappears, warning stops. 

6. Temperature Calibration Function   

When there is tolerance between the measured temperature and real temperature, set parameter U20 and 

u21 to calibrate. The calibration range is ±9.9

. When set the parameter, the step is 0.1

 for every key 

press. Keep pressing, the set data will increase/decrease quickly. 

7. Restore the default password   

When password forgotten, the following way can restore it:

  Press and hold

“▲”

and 

“▼”

key, turn on 

the power supply, the device displays 

UnL

, after three seconds, buzzer sounds, system auto restores 

the default password

11

8. Controller Installation 

8.1 Warning 

Avoid installing the device in the following environment: 

● Relative humidity is greater than 90%, or possibly dewing. ● Strong vibration . 

Summary of Contents for ZL-310A

Page 1: ... Power Supply 185 245VAC 50 60HZ Terminal Wire 2 1 5mm2 or 1 2 5mm2 Load Current 3A 250Vac Resistive load Case PC ABS Fire Proof Protection Degree IP30 4 Operation Instruction 4 1 Display Indication Panel LED Indication LED On Off Blinking MAX TEMP Set max temperature Set max temperature to be set MIN TEMP Set min temperature Set min temperature to be set COOL Compressor on Compressor off Delay pr...

Page 2: ...he parameter code Press SET will show the parameter value Then press or to set this parameters and press SET to return The factory setting password is 11 Exit the Mode Keep depressing SET for three seconds the set parameters will be saved the mode exits Or do not press any key for 30 seconds the mode exits and the set parameters are not saved Parameter Code and Description Table N o Parameter code...

Page 3: ...or U12 3 minutes stop for 30 U12 3 minutes Note If U12 0 system stops when sensor fails 5 4 High temperature and Low temperature warning When the test temperature MAX TEMP U50 and the time reaches to U52 or U53 high temperature warning starts When the test temperature MIN TEMP U51 and the time reaches to U52 or U53 low temperature warning starts 5 5 External input warning There are several ways fo...

Page 4: ...cian Wrong power supply may damage the device and system seriously Try with effort to layout the sensors and switches line apart from inductive load lines and power supply lines The sensors and switches lines are not allowed go with the power supply lines and inductive load lines in a same pipeline and are not allowed to pass near the contactor breaker and the similar Reduce the length of sensors ...

Reviews: