
SMAX - SSI and analogue
5.2.5 STOP
input
It is used to execute the TEACH-IN procedure. It is active at HIGH logic level
(voltage greater than 10V must be applied). For any further information on
using the
START
and
STOP
inputs refer to the “5.3 TEACH-IN procedure”
section on page 24.
5.2.6 Fault output
The Fault output is only available for AI1 current analogue output and is
intended to signal an error condition such as a circuit break.
To connect the Fault signal please refer to the examples in the sections
hereafter: “5.2.6.1 Fault output connected to a PLC input“ and “5.2.6.2 Fault
output connected to a relay“.
Please pay attention to the value of the R2 resistor (Figure 3 and Figure 4).
Imax = 50 mA
R1 = 47
R1
I
Vdc
R2
No encoder error = transistor ON (conducting)
Encoder error = transistor OFF (open)
5.2.6.1 Fault output connected to a PLC input
Figure 3
No encoder error = PLC input Low (0Vdc)
Encoder error = PLC input High (+Vdc)
MAN SMAX SSI_AI1_AV2 E 1.5.odt
5 - Analogue interface
22 of 32