LD30x
7.3 Model LD301: additional settings for the analogue output
The Basic menu provides the following additional settings:
Menu
Setting Range
Default
A-ChAr
Analogue characteristics
Select one of the following options:
0_10
+/-10 V (bipolar)
-10_10
0-10 V (positive output only)
0_10
4-20 mA current output.
4_20
0-20 mA current output
0_20
When you set the output to +/-10 Volts, your input
signals A/B must be of quadrature type with phase
displacement. The polarity of the output follows
the sign in the display (operation as a counter or as
a speed display with detection of direction of
rotation).
OFFSEt
Analogue Offset *
Set this register to “0” when your output range
should begin at zero (or 4 mA) If you desire another
initial output value, set this register
correspondingly. Setting 5.000 means your output
will start at 5 Volts instead of zero.
-9.999 ... +9.999
0.000
GAin
Analogue Gain *
Set the analogue stroke you desire: setting 1000
means 10 Volts or 20 mA. Setting 200 reduces the
stroke to 2 Volts or 4 mA.
00.00 ... 99.99
10.00
* See next page for more details.
Response time of the analogue output:
Operation mode
Response time analogue output
Tachometer, frequency meter (see section “7.2.1
RPM, operation as tachometer or frequency
counter” on page 16)
330ms at f >3Hz
1/f at f < 3Hz
Baking time / processing time indicator (see
section “7.2.2 Time, display of baking or processing
time (reciprocal speed)“on page 17)
330ms at f >3Hz
1/f at f < 3Hz
Timer, Stopwatch (see section “7.2.3 Timer,
Stopwatch“ on page 18)
7 ms
(With latch function after every measurement)
Counter for position or event (see section “7.2.4
Count, Counter mode“ on page 19)
Counter value + 7ms
Speed calculation from differential transition time
(see section “7.2.5 Speed from differential time
between a Start and a Stop input“ on page 20)
R 7ms
The analogue output behaves like the display output.
MAN LD30x E 1.0.odt
Set up procedure
21 of 40