Chapter_3. Configuration
Page.5
LED
KEY
LCD
3.2 Key
(1) Key usage
3.1 LED
Setting mode
Key
1S
1L
2S
2L
3S
3L
A
B
G
S1
S2
G
P1
P2
P3
P0
KDX-300
PT Input
AC 40 ~ 500V
CT Input
0.1 ~6A
Source
AC 90~260V, DC 110V
Panel Power Meter
DIsplay mode
page down
page up
Page down
Page up
Harmonic mode
Page down
Page up
Switch to basic mode
3.3 LCD
- Clear large LCD display with white backlight.
3.4 Terminals
Terminals
S1, S2, G
P1, P2, P3, P0
1S, 1L, 2S, 2L, 3S, 3L
A+, B-, SG
Usage
Aux. power / Earthing
Voltage input
Current input
RS-485 communication (to PC)
This device is equipped with 5 LED on the front top, which help to recognize power consumption easily.
Return to first page.
Or switch to setting mode
with holding 2 sec
Set-up ready
Set-up complete
Increase value.
Or rapid increase with holding 2 sec.
Decrease value.
Or rapid decrease with holding 2 sec.
Tap down(19>15>12>8>5>1 page)
Tap up(1>5>8>12>15>19 page)
Tap up(1>17 page)
Tap down(17>1 page)