Lightsafe_EBLEDPT_Instructions_Rev01
If fitting does not complete the required emergency duration the LED will then flash Red three times every
three seconds.
Manual Test
The luminaire has a test button underneath the fitting which has two functions;
1.
When the button is pressed once, the schedule of self-test will be reset (i.e. from the 1
st
day
installed).
2.
When the button is pressed for three seconds, the fitting will enter a self-test mode for 10 minutes
with the same LED color indication as the monthly/annual test (red flashing quickly).
LED Indicator Status
Green LED On:
AC mains supply and battery connected
LED Off:
No AC supply present
Red Flash
Once
every 3 seconds: Issue with the battery during the daily test
Red Flash very quickly:
Luminaire in manual/monthly/annual test mode
Red Flash
Twice
every 3 seconds: Fitting failed test - Issue with the light output during auto-test
Red Flash
Three
every 3 seconds: Fitting failed test – the battery duration was not achieved during auto-
test
Failed Test / Reset:
After a failed test and the fault has been rectified, the test button will
need to be pressed for 3 seconds to activate a self-test or remove the
230v AC supply to reset the fault and LED indicator status back to green.
Maintenance
Repairs should only be carried out by suitably qualified person
Regular cleaning of luminaires should be carried out at regular intervals not only to ensure good optical
performance but also ensure that dirt does not accumulate to such an extent as to impair the electrical or
thermal safety of the fitting, this should be done with a soft damp cloth, do not use any chemicals or
abrasives.
Servicing should only be carried out after the fitting has been made electrically safe and the battery
disconnected.
Light Source Maintenance:
the light source of this luminaire is not replaceable; in case the light source
need to be replaced (e.g. at the end of its life), the whole luminaire shall be replaced.
TESTING
Ensure the luminaires are tested in accordance with 5266-8:2004 / BS EN 50172:2004
Daily:
Ensure the green charge LED is illuminated
Monthly:
Check the LED Indicator Status, if Green then the unit has passed the monthly test. If the LED is
flashing 2 or 3 times every 3 seconds then then luminaire has failed and will require an engineer
to investigate, record the result in the log book
Annually:
Repeat the monthly inspection and record the result in the log book. If the LED is flashing 2 or 3
times every 3 seconds then then luminaire has failed and will require an engineer to investigate.
Defects:
Any defects or failures should be noted and recorded in the log book and actioned by a
competent person as soon as possible
Environment:
Please DO NOT dispose of electrical items or packaging as unsorted waste, use the recycling facilities
provided by your local authorities.