LIGHTSAFE EBLEDPT Quick Start Manual Download Page 2

Lightsafe_EBLEDPT_Instructions_Rev01 

7.

 

The battery needs to be connected, remove the screw from the side of the fitting, unclip the top of 

the fitting, plug in the battery, the date of installation should be added to the label on the battery 

and re-assemble 

8.

 

Restore the mains supply, the green LED should be illuminated 

9.

 

Allow 24 hour to charge the batteries and record the installation date in the log book 

10.

 

After a 24 hour charge period test the luminaire for a full 3 hour duration by removing the 230v AC 

supply and record the date of the commissioning on the battery pack inside the luminaire and also 

in the log book 

11.

 

Subsequent testing should be carried out in accordance with the British/European standards and 

recorded in the log book 

 

Installation Method A - To adjust the length of the supporting cables wires, push the spring loaded metal 
tube that the wire feeds through on the ceiling mount holder and adjust accordingly, releasing the tube 
locks the supporting cable wire

 

 
Automatic Self-Test Function  

The luminaire has an integral automatic self-test function. 

When the luminaire is connected to a 230v AC supply the luminaire will perform an automatic test, monthly 

and  annually.    The  first  monthly  test  will  be  performed  approximately  between  16

th

  to  30

th

  day  and  the 

annual test will be between 200

th

 to 360

th

 day from initial power on.   

After the first annual test, the test routine will then be scheduled for every 30 days and every 360 day for 

the  monthly  and  annual  tests.    The  luminaire  will  retain  the  testing  schedule  for  approximately  7  days 

without a 230v AC supply (the internal battery still has to be connected). 

    

Automatic Daily Test 

The  luminaire  checks  daily  if  the  battery  is  connected  and  that  AC  mains  supply  is  present,  if  both  are 

present the  GREEN LED will be illuminated.  If the battery is not connected or there is an issue with the 

battery  the  LED  will  flash  Red  once  every  three  seconds.    If  there  is  no  230v  AC  supply  present  the  LED 

indicator will be extinguished and the luminaire will be in emergency mode. 

 

Monthly /Annual Test 

The luminaire performs an automatic 10 minutes duration self-test every month and an annual test for the 

full 3 hours duration.  During the test the LED will be flashing RED quickly to indicate the fitting is in test for 

the  duration  of  the  test,  if  the  test  has  been  completed  and  satisfactorily  then  the  LED  will  return  to  a 

constant Green state. 

If  during  the  test  there  is  an  issue  with  the  light  output,  then  the  LED  will  flash  Red  twice  every  three 

seconds. 