Lightsafe_EBLEDPT_Instructions_Rev01
7.
The battery needs to be connected, remove the screw from the side of the fitting, unclip the top of
the fitting, plug in the battery, the date of installation should be added to the label on the battery
and re-assemble
8.
Restore the mains supply, the green LED should be illuminated
9.
Allow 24 hour to charge the batteries and record the installation date in the log book
10.
After a 24 hour charge period test the luminaire for a full 3 hour duration by removing the 230v AC
supply and record the date of the commissioning on the battery pack inside the luminaire and also
in the log book
11.
Subsequent testing should be carried out in accordance with the British/European standards and
recorded in the log book
Installation Method A - To adjust the length of the supporting cables wires, push the spring loaded metal
tube that the wire feeds through on the ceiling mount holder and adjust accordingly, releasing the tube
locks the supporting cable wire
Automatic Self-Test Function
The luminaire has an integral automatic self-test function.
When the luminaire is connected to a 230v AC supply the luminaire will perform an automatic test, monthly
and annually. The first monthly test will be performed approximately between 16
th
to 30
th
day and the
annual test will be between 200
th
to 360
th
day from initial power on.
After the first annual test, the test routine will then be scheduled for every 30 days and every 360 day for
the monthly and annual tests. The luminaire will retain the testing schedule for approximately 7 days
without a 230v AC supply (the internal battery still has to be connected).
Automatic Daily Test
The luminaire checks daily if the battery is connected and that AC mains supply is present, if both are
present the GREEN LED will be illuminated. If the battery is not connected or there is an issue with the
battery the LED will flash Red once every three seconds. If there is no 230v AC supply present the LED
indicator will be extinguished and the luminaire will be in emergency mode.
Monthly /Annual Test
The luminaire performs an automatic 10 minutes duration self-test every month and an annual test for the
full 3 hours duration. During the test the LED will be flashing RED quickly to indicate the fitting is in test for
the duration of the test, if the test has been completed and satisfactorily then the LED will return to a
constant Green state.
If during the test there is an issue with the light output, then the LED will flash Red twice every three
seconds.