3 Hours Maintained Emergency Blade Drop Light c/w Automatic Self-Test Function 

 

 

 

 

 

 

 

 

Please read these instructions before installation and retain for the user/maintenance engineer for future 

reference.  

 

IMPORTANT NOTE:  

The luminaire must be installed by a skilled electrician and to the most current electrical wiring and building 

regulations  

This product 

MUST

 be earthed 

 and 

NOT

 be subject to an electrical insulation test (500/1000v) which 

will not be covered by the warranty 

This luminaire is NOT suitable to be used with dimmer switches 

The luminaire should not be modified, if modified this will invalidate any warranties and Firesafe will not be 

liable for any damages caused. 

The person carrying out the installation is to check and verify that the total load on the circuit, including the 

rating of the cable, fuse and/or circuit breaker is not exceeded 

It is the responsibility of the installer to consider any fire risks and breach in any fire protection barriers or 

partitions, and take the appropriate precautions 

Emergency lighting should be installed and maintained in accordance with BS5266 and BS EN50172 

 

INSTALLATION 

1.

 

Select the correct legend to be fitted 

2.

 

Ensure the mains supply is switched off 

3.

 

To change the legend remove the 3 screws at the bottom diffuser, insert the new legend ensuring 

the top of the legend slides between the diffuser and the top of the fitting and refit the LED plate 

ensuring the plate is correctly located and the screws fully tightened 

4.

 

The fitting requires a permanent 230v AC supply to the live, L Brown, Earth  

 yellow/Green and 

neutral, N Blue wires 

5.

 

For the maintained circuits for continuous illumination of the light this can be achieved by 

connecting the Live to (L Brown) and Switch Live (Ls Black) together or for switch maintained 

operation connect a switch live (Ls black) through a remote switch 

6.

 

Connect the supply cables to the appropriate wires of the unit and ensure that ALL electrical 

connections are tight with no loose strands  

 