![LIGHTSAFE EBLEDPT Quick Start Manual Download Page 1](http://html1.mh-extra.com/html/lightsafe/ebledpt/ebledpt_quick-start-manual_1915068001.webp)
Lightsafe_EBLEDPT_Instructions_Rev01
EBLEDPT
3 Hours Maintained Emergency Blade Drop Light c/w Automatic Self-Test Function
Please read these instructions before installation and retain for the user/maintenance engineer for future
reference.
IMPORTANT NOTE:
The luminaire must be installed by a skilled electrician and to the most current electrical wiring and building
regulations
This product
MUST
be earthed
and
NOT
be subject to an electrical insulation test (500/1000v) which
will not be covered by the warranty
This luminaire is NOT suitable to be used with dimmer switches
The luminaire should not be modified, if modified this will invalidate any warranties and Firesafe will not be
liable for any damages caused.
The person carrying out the installation is to check and verify that the total load on the circuit, including the
rating of the cable, fuse and/or circuit breaker is not exceeded
It is the responsibility of the installer to consider any fire risks and breach in any fire protection barriers or
partitions, and take the appropriate precautions
Emergency lighting should be installed and maintained in accordance with BS5266 and BS EN50172
INSTALLATION
1.
Select the correct legend to be fitted
2.
Ensure the mains supply is switched off
3.
To change the legend remove the 3 screws at the bottom diffuser, insert the new legend ensuring
the top of the legend slides between the diffuser and the top of the fitting and refit the LED plate
ensuring the plate is correctly located and the screws fully tightened
4.
The fitting requires a permanent 230v AC supply to the live, L Brown, Earth
yellow/Green and
neutral, N Blue wires
5.
For the maintained circuits for continuous illumination of the light this can be achieved by
connecting the Live to (L Brown) and Switch Live (Ls Black) together or for switch maintained
operation connect a switch live (Ls black) through a remote switch
6.
Connect the supply cables to the appropriate wires of the unit and ensure that ALL electrical
connections are tight with no loose strands