Instructions

 

for Recessed ProSpec

 Track

Power Feed to Track

DIRECT POWER FEED TO "FEED" TRACK

Use solid 12 ga. copper wire when feeding the track. The feed track accepts
two separate 120 V, 60 Hz branch circuits. Each circuit must not exceed the
20 amp capacity of the track system.

FEED FROM ABOVE TRACK 

 (Fig E)

:

•Remove Bottom cover and save.

•Remove Knockout in Top Plate.

•Remove Top Plate from Track

•Secure electrical connector (by others; 

3

/

8

 size recommended) to Top

Plate using the Nut provided. Position connector locking screws such
that the screws will be hidden behind the track width.

•Attach Top Plate to track.

•Pass wires through connector and secure the cable or conduit to the

connector. 

The track must not support the cable. Use separate support

for securing the cable to the building structure.

•Secure the track to the ceiling (

see mounting on previous page).

•Form the wires in the Feed track to the connector terminals

(see FIG. F). Cut and strip each wire. Attach wires to the screw
terminals. Wires must be tightly held in the screw terminals. Neutral
wires must be attached to screw terminals marked "NEUT”. Ground
wire must be attached to the green ground screw.

•Snap Bottom Cover into the track.

FIG. G

A0397

Page 3 of 4

Electrical

Connector

Knock out

Feed Track

Top Plate

Bottom Cover

FIG. E

Use 12 ga. solid copper wire for feed
connections including ground.

Two wires may be
attached to one
screw terminal.

Circuit 2

Neutral 2

FIG. F

Circuit 1

Neutral 1

.50

Ground Terminal

Power
Terminals

Neutral
Terminals

Wire Cover

Feed End

Floating Splice Box

Dead End

Feed Track Unit

FEEDING ALONG THE TRACK LENGTH

 (Fig. G)

A floating splice box may be used to feed the "Feed Track" from along the
tracks length. The floating splice box can be mounted anywhere on the track
up to 4' from the end of the track. The wires are passed along the top of the
track and into the feed end of the track. 

The floating splice box may

only be used when there is accessibility to the splice box after the
installation is complete.

Floating Splice Box (Cat. no. 26660) sold separately. See instructions
supplied with 26660 for complete installation  details.

Summary of Contents for ProSpec Track Lighting

Page 1: ...S Read all Track Connector Feed in Kits and Accessory Instruction Sheets before installing any ProSpec Track item When installing or using this track system basic safety precautions should be followed Read all instructions before installing the track system Do not install in wet media concrete plaster etc This track system is intended for installation in accordance with the National Electrical Cod...

Page 2: ...Clips sold separately Cat 26090 set of 4 Fig C Slide or snap the hanger clips onto the track Assemble the screws and nuts onto the mounting clips Recommended two clips per 4 track three clips per 8 track and four per 12 track Always use more then one clip per track length Additional clips may be added for more support The clips should be evenly spaced along the track length Tighten the clip on the...

Page 3: ...strip each wire Attach wires to the screw terminals Wires must be tightly held in the screw terminals Neutral wires must be attached to screw terminals marked NEUT Ground wire must be attached to the green ground screw Snap Bottom Cover into the track FIG G A0397 Page 3 of 4 Electrical Connector Knockout FeedTrack Top Plate Bottom Cover FIG E Use 12 ga solid copper wire for feed connections includ...

Page 4: ...r or by using Plain Track with multiple Power Extensions The Power Extension Connector is sold separately CAT NO 26646WH See instructions with the power extension for installation details NOTE THIS TRACK SYSTEM IS NOT POLARIZED Connectors can be installed into both sides of the Plain Track and in any orientation There is no key that will prevent insertion of the connectors Connectors cannot be att...

Reviews: