READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE

This fixture is intended for installation in accordance with the National Electrical Code and local regulations.  To

assure full compliance with local codes and regulations, check with your local electrical inspector before

installation.  To prevent electric shock, turn off electricity at fuse box before proceeding.

Retain these instructions for maintenance reference.

INSTRUCTION SHEET NO.

IS:4X9EM

A0502

Page 3 of 4

 

COMPANY

631 Airport Road, Fall River, MA 02720

Instructions for replacing EMERGENCY BALLAST:

ALL SERVICING MUST BE PERFORMED BY QUALIFIED PERSONNEL ONLY.

1.  This unit has more than one power supply connection point. Make certain that the switch (if the fixture is switched) and

the unswitched lines to the EMERGENCY BALLAST are turned off at the fuse box.

2.  To remove SWITCH BOX from ceiling: Disconnect the battery pack inverter connectors (see page 2) located inside the

SWITCH BOX  to prevent electrical shock from the battery pack.  Disconnect switch and indicator light leads, and
locknut inside SWITCH BOX. Remove SWITCH BOX.

3.  Disconnect all EMERGENCY BALLAST connections inside fixture JUNCTION BOX.
4.  Disconnect all leads from A/C BALLAST.  DO NOT disconnect any wire leads from lamp socket(s). Remove LOCKNUT

from BALLAST PLATE, and remove BALLAST PLATE with A/C BALLAST. See page 2 for detailed instructions on A/C
BALLAST removal and replacement.

5.  Loosen RETAINING SCREW on EMERGENCY BALLAST MOUNTING BRACKET, and lift EMERGENCY BALLAST

MOUNTING BRACKET  from HOUSING wall.

6.  Feed EMERGENCY BALLAST MOUNTING BRACKET and EMERGENCY BALLAST through opening.
7.  Remove emergency ballast from MOUNTING BRACKET and replace with new EMERGENCY BALLAST.
8.  Re-install all hardware, including fiberglass sleeves over wiring.
9.  Re-connect all electrical connections. Follow appropriate wiring diagram on page 4.

SWITCH BOX

JUNCTION BOX

A/C BALLAST

BALLAST PLATE

LOCKNUT

HOUSING

RETAINING SCREW

EMERGENCY BALLAST
MOUNTING BRACKET

VIEW LOOKING INSIDE FIK

SIDE VIEW

INSTALLATION PROCEDURE FOR: 4X9 AND 9X9 

MATRIX

 SERIES RECESSED

COMPACT FLUORESCENT EMERGENCY LIGHTING FRAME-IN KITS

EMERGENCY
BALLAST

Summary of Contents for 4X9 MATRIX SERIES

Page 1: ...If acid is spilled on skin or eyes flush with fresh water and contact a physician immediately 5 Equipment should be mounted in locations and at a height where it will not be readily subject to tampering by unauthorized personnel 6 The use of accessory equipment is not recommended by the manufacturer and may cause an unsafe condition 7 Do not use the equipment for other than intended use 8 This uni...

Page 2: ... the EMERGENCY BALLAST see page 3 are turned off at the fuse box 2 Disconnect the battery pack INVERTER CONNECTORS Fig 1 located inside the SWITCH BOX see page 3 to prevent electrical shock from the battery pack 3 Remove REFLECTOR TRIM lamp s See IS 4X4 section E 4 Undo WINGNUT s and remove UPPER REFLECTOR 5 Remove SCREWS that secure BALLAST PLATE to HOUSING 6 Partially remove BALLAST PLATE from H...

Page 3: ...cal shock from the battery pack Disconnect switch and indicator light leads and locknut inside SWITCH BOX Remove SWITCH BOX 3 Disconnect all EMERGENCY BALLAST connections inside fixture JUNCTION BOX 4 Disconnect all leads from A C BALLAST DO NOT disconnect any wire leads from lamp socket s Remove LOCKNUT from BALLAST PLATE and remove BALLAST PLATE with A C BALLAST See page 2 for detailed instructi...

Page 4: ...MMON GROUND HOT SWITCHED OR UNSWITCHED EMERGENCY PACK A C BALLAST JUNCTION BOX LAMP 2 TEST SWITCH INDICATOR LIGHT VIOLET WHT BLK BLK VIOLET W H T WHT BLK WHT RED WHT 1 SWITCH BOX LAMP BLU BLU WHT WHT BLK WHT BLK 120 V ORG 277 V RED YEL BLK YEL B B R R Y Y W G B GRN BLK WHT BLK 120 V ORG 277 V HOT UN SWITCHED 120V BLK OR 277V ORG CAP UNUSED LEAD COMMON GROUND HOT SWITCHED OR UNSWITCHED EMERGENCY PA...

Reviews: