ciRcUiT bREAkER REqUiREMENTS:
A new gFCI circuit breaker must be used for your spa installation. Do not use an existing breaker,
as its condition is unknown.
bREAKER 230v
Capacity
32 amps
# of wires
4
On 230V systems always use a 4 wire system. ON all systems, the spa must be connected to a
dedicated gFCI circuit breaker that is not shared with any other equipment. Do not use extension
or plug type cords of any kind.
cONFigURiNg SYSTEM
iNPUT VOLTAgE
This Power System is supplied to utilize a 230V power supply (2 hot wires, a neutral wire, and a
ground wire). Dip switch # 2 must be set to the “On” position. When configured to operate at 230V,
the heater is rated at 4.0kW and will heat whenever heat is required.
When configuring the output voltages on your System, remember to also consider the amperage
of each component. Be sure that the total amperage draw does not exceed the capability of the
circuit supply and power to the system.
NOTE:
The Coronado is configured to have three operational modes. It has been pre-
programmed to operate in the Standard Operational Mode ONLY. To change your spa to allow 3
different modes, we recommend you contact customer service and schedule service. Dip Switch
#7 on the control box board must be moved down into the “off” position allowing you to select
either Standard, Economy, or Sleep modes using the topside control panel.
ON/UP
Dip Switches
1 2 3 4 5 6 7 8 9 10
ELECTRICAL REqUIREMENTS