RC Series Rackmount Installation Manual
12
13
Electrical Specifications
LifeSafety Power, Inc .
750 Tower Road, Unit B
Mundelein, IL 60060 USA
www .lifesafetypower .com
Tel (888) 577-2898
info@lifesafetypower .com
Important:
All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitabil-
ity of each product for their particular application. LifeSafety Power makes no warranties as to the accuracy or completeness of the informa-
tion, and disclaims any liability regarding its use. LifeSafety Power’s only obligations are those in the LifeSafety Power Standard Terms
and Conditions of Sale for this product, and in no case will LifeSafety Power or its distributors be liable for any incidental, indirect, or conse-
quential damages arising from the sale, resale, use, or misuse of the product. Specifications are subject to change without notice. In ad-
dition, LifeSafety Power reserves the right to make changes—without notification to Buyer—to processing or materials that do not affect
compliance with any applicable specification.
LifeSafety Power, FlexPower, DataLink, PowerCom, and VSelect are trademarks or registered trademarks of LifeSafety Power Inc . or its affiliates .
© 2015 LifeSafety Power Inc
. P03-050 Rev A03 02/16
RC Series Rackmount Power Supplies - continued
Specifications
RC250 Series
RC250B Series
AC Input
Voltage
120/230VAC
±15% at 50-60Hz
120/230VAC
±15% at 50-60Hz
Power
300 Watts
300 Watts
Standby
Current
100mA
100mA
Rated Current for
UL603 Proprietary
Alarm Installations
Current
2 .5A maximum from
all circuits in system
2 .5A maximum from
all circuits in system
DC Output
Voltage
12 .5V and 25 .0V ±0 .5V
nominal
12 .5V and 25 .0V ±0 .5V
nominal
Max Current
20A@12V and 10A@24V 4A@12V and 8A@24V
Ripple
120mV
120mV
Regulation
±2%
±2%
Efficiency
89% (120VAC 60Hz In,
Full Load, No Batt)
89% (120VAC 60Hz In,
Full Load, No Batt)
Battery
Size & Type
4-80AH Lead Acid
or Gel Cell
4-80AH Lead Acid
or Gel Cell
Charge Current
2A (±10%) Maximum 2A (±10%) Maximum
Fuse Ratings
DC1 (Internal)
ATM 30A
ATM 30A
DC2 (Internal)
ATM 30A
ATM 30A
Battery (Internal)
ATM 30A
ATM 30A
Distributed Zones
ATM 3A
ATM 3A
BTU Output
BTU
109
109
Fault Setpoints
Low AC
95V (±6%)
95V (±6%)
Earth GND
2000 Ohms
2000 Ohms
Output Voltage
±10% of Nominal
±10% of Nominal
Batt Voltage
±10% of Nominal
±10% of Nominal
Batt Presence
6–15V (12V Setting),
11–29V (24V Setting)
6–15V (12V Setting),
11–29V (24V Setting)
Fault Relay
Contacts
AC FLT
1A at 24VDC
1A at 24VDC
SYS FLT
1A at 24VDC
1A at 24VDC
Distributed Outputs
Count
8 or 16
8 or 16
Current Fused
3A
3A
Current PTC
2 .5A
2 .5A